EA-330AE10-C05 C
6.31 kW
Defrost: None
Product code: EA-145AC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,338 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 16.7 m² |
| Inner volume | 5.7 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 45 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-145AC7-C01 C | None |
|---|---|
| EA-145AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.48 | 2.49 | 2.50 | 2.50 | 2.47 | 2.44 | 2.39 | 2.41 | 2.54 | 2.72 | 2.63 | 2.60 | 2.55 | 2.47 |
| 5 | 3.23 | 3.31 | 3.36 | 3.41 | 3.42 | 3.40 | 3.35 | 3.37 | 3.57 | 3.84 | 3.71 | 3.67 | 3.61 | 3.51 |
| 6 | 3.91 | 4.09 | 4.23 | 4.36 | 4.42 | 4.43 | 4.39 | 4.42 | 4.68 | 5.05 | 4.88 | 4.82 | 4.73 | 4.60 |
| 7 | 4.48 | 4.73 | 4.95 | 5.11 | 5.24 | 5.32 | 5.35 | 5.42 | 5.76 | 6.25 | 6.11 | 6.05 | 5.95 | 5.78 |
| 8 | 5.00 | 5.33 | 5.60 | 5.86 | 6.05 | 6.16 | 6.22 | 6.31 | 6.71 | 7.29 | 7.13 | 7.06 | 6.96 | 6.80 |
| 9 | 5.47 | 5.86 | 6.24 | 6.59 | 6.84 | 7.00 | 7.10 | 7.21 | 7.67 | 8.34 | 8.17 | 8.09 | 7.98 | 7.79 |
| 10 | ≈ 5.80 | 6.37 | 6.86 | 7.29 | 7.61 | 7.83 | 7.97 | 8.11 | 8.63 | 9.39 | 9.21 | 9.13 | 9.01 | 8.79 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 9.214 |
| SC2 | 0 | 8 | 6.311 |
| SC3 | -18 | 7 | 5.171 |
| SC4 | -25 | 6 | 4.234 |
| SC5 | -34 | 6 | 3.955 |
| A | 1067 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E | 735 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1067 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.