EA-235AE7-C01 C
8.19 kW
Defrost: None
Product code: EA-145AE7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 4,763 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 25.0 m² |
| Inner volume | 8.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 53 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EA-145AE7-C01 C | None |
|---|---|
| EA-145AE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.29 | 3.33 | 3.37 | 3.39 | 3.38 | 3.34 | 3.29 | 3.35 | 3.55 | 3.84 | 3.72 | 3.68 | 3.61 | 3.52 |
| 5 | 4.22 | 4.32 | 4.44 | 4.53 | 4.56 | 4.54 | 4.49 | 4.55 | 4.82 | 5.21 | 5.04 | 4.99 | 4.91 | 4.80 |
| 6 | 5.05 | 5.30 | 5.51 | 5.69 | 5.78 | 5.80 | 5.76 | 5.82 | 6.17 | 6.67 | 6.45 | 6.37 | 6.24 | 6.05 |
| 7 | 5.77 | 6.11 | 6.42 | 6.69 | 6.83 | 6.93 | 6.97 | 7.07 | 7.51 | 8.16 | 7.93 | 7.83 | 7.68 | 7.43 |
| 8 | 6.41 | 6.87 | 7.23 | 7.59 | 7.84 | 8.00 | 8.07 | 8.18 | 8.70 | 9.45 | 9.21 | 9.11 | 8.96 | 8.71 |
| 9 | 6.99 | 7.51 | 8.04 | 8.50 | 8.83 | 9.04 | 9.16 | 9.31 | 9.89 | 10.75 | 10.50 | 10.38 | 10.21 | 9.91 |
| 10 | ≈ 7.51 | 8.15 | 8.80 | 9.38 | 9.79 | 10.08 | 10.24 | 10.43 | 11.09 | 12.05 | 11.79 | 11.66 | 11.47 | 11.12 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.791 |
| SC2 | 0 | 8 | 8.184 |
| SC3 | -18 | 7 | 6.770 |
| SC4 | -25 | 6 | 5.511 |
| SC5 | -34 | 6 | 5.109 |
| A | 1067 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E | 735 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 1067 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.