EA-440AG4-C01 C
26.78 kW
Defrost: None
Product code: EA-163FG4-C08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,888 m³/h |
|---|---|
| Air throw | 31 m |
| External surface | 167.1 m² |
| Inner volume | 34.9 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 186 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-163FG4-C08 C | None |
|---|---|
| EA-163FG4-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.76 | 11.70 | 11.68 | 11.71 | 11.67 | 11.60 | 11.48 | 11.71 | 12.47 | 13.51 | 13.24 | 13.15 | 13.03 | 12.80 |
| 5 | 15.01 | 15.09 | 15.18 | 15.25 | 15.23 | 15.13 | 14.96 | 15.16 | 16.10 | 17.42 | 16.97 | 16.81 | 16.60 | 16.29 |
| 6 | 18.14 | 18.46 | 18.74 | 18.98 | 19.03 | 18.94 | 18.71 | 18.88 | 20.00 | 21.61 | 20.95 | 20.70 | 20.36 | 19.84 |
| 7 | 21.10 | 21.74 | 22.20 | 22.65 | 22.85 | 22.83 | 22.63 | 22.75 | 24.09 | 26.02 | 25.14 | 24.81 | 24.32 | 23.55 |
| 8 | 23.70 | 24.64 | 25.50 | 26.25 | 26.69 | 26.84 | 26.67 | 26.80 | 28.35 | 30.63 | 29.58 | 29.17 | 28.55 | 27.54 |
| 9 | 26.04 | 27.34 | 28.50 | 29.50 | 30.12 | 30.42 | 30.45 | 30.71 | 32.55 | 35.24 | 34.17 | 33.67 | 32.93 | 31.69 |
| 10 | 28.21 | 29.89 | 31.40 | 32.69 | 33.51 | 33.95 | 34.06 | 34.36 | 36.42 | 39.41 | 38.31 | 37.82 | 37.08 | 35.83 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 10.05 | 10.70 | 11.61 | 11.39 | 11.31 | 11.21 | 11.08 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 13.62 | 14.75 | 14.38 | 14.25 | 14.07 | 13.80 |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | 18.70 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | 21.64 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | 24.39 | 25.03 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | 26.93 | 27.81 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 38.310 | — |
| SC2 | 0 | 8 | 26.796 | — |
| SC3 | -18 | 7 | 22.762 | — |
| SC4 | -25 | 6 | 18.740 | — |
| SC5 | -34 | 6 | 18.231 | — |
| A | 1415 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| G | 1135 mm |
| E | 1035 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 1415 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.