Skip to Content

Unit cooler EA-180GC4-C01 C

Unit cooler EA-180GC4-C01 C
Illustrative photo

Producer: Karyer · Line: EA (General)

Product code: EA-180GC4-C01 C

Cooling capacity i
25.06 kW
Air flow
20,540 m³/h
Fin spacing
4.6 mm
Air throw
38 m
Fans
1 × ⌀800 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Data

Evaporator
Air flow 20,540 m³/h
Air throw 38 m
External surface 130.3 m²
Inner volume 27.2 dm³
Fin spacing 4.6 mm
Fin materialAluminium
Net weight 201 kg
Fans
Quantity 1
Diameter 800 mm
Speed 900 rpm
Power 1,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 80.0 dB(A)
Energy class E
Connections
Inlet Ø28
Outlet Ø42
Defrost
EA-180GC4-C01 C None
EA-180GC4-C01 C ED Electric

Performance

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
25.056 kW
Low speed (Y)
20.918 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 10.53 10.41 10.38 10.37 10.31 10.23 10.14 10.24 10.84 11.71 11.43 11.32 11.18 10.96
5 13.58 13.67 13.75 13.81 13.77 13.66 13.51 13.61 14.42 15.57 15.16 15.02 14.82 14.51
6 16.55 16.92 17.15 17.39 17.45 17.39 17.23 17.31 18.33 19.77 19.20 18.99 18.70 18.26
7 19.15 19.80 20.40 20.92 21.24 21.32 21.21 21.29 22.54 24.32 23.58 23.31 22.91 22.28
8 21.44 22.40 23.27 24.02 24.48 24.74 24.83 25.06 26.59 28.83 28.15 27.89 27.43 26.65
9 23.56 24.88 26.06 27.07 27.72 28.11 28.27 28.54 30.29 32.85 32.08 31.76 31.29 30.52
10 25.52 27.22 28.74 30.05 30.93 31.47 31.74 32.06 34.04 36.93 36.07 35.71 35.16 34.26

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 9.06 8.96 8.91 8.91 8.87 8.82 8.75 8.90 9.46 10.24 10.02 9.94 9.82 9.65
5 11.69 11.66 11.67 11.68 11.65 11.57 11.46 11.59 12.31 13.32 13.00 12.89 12.73 12.50
6 14.26 14.40 14.54 14.66 14.66 14.57 14.42 14.52 15.39 16.63 16.17 16.00 15.77 15.41
7 16.74 17.12 17.38 17.65 17.75 17.71 17.56 17.64 18.68 20.17 19.55 19.32 18.99 18.48
8 18.95 19.56 20.13 20.64 20.92 20.96 20.84 20.92 22.14 23.92 23.16 22.87 22.45 21.77
9 20.92 21.80 22.58 23.28 23.70 23.92 23.97 24.17 25.64 27.79 26.95 26.59 26.08 25.24
10 22.77 23.93 24.98 25.88 26.45 26.76 26.87 27.10 28.74 31.15 30.36 30.03 29.53 28.71

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 36.07130.360
SC2 0 8 25.05620.918
SC3 -18 7 21.06917.709
SC4 -25 6 17.14514.537
SC5 -34 6 16.65214.314

Dimensions

Dimension drawing of EA-180GC4-C01 C
Dimension drawing
Dimensions as drawn
A 1715 mm
B 950 mm
C 1430 mm
F 910 mm
G 1015 mm
E 1335 mm
D IN 1 x Ø28
D OUT 1 x Ø42
Overall [mm]
Length 1715 mm
Width 1000 mm
Height 1430 mm

Downloads