EA-263EC7-C11 C
24.78 kW
Defrost: None
Product code: EA-180GE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 20,482 m³/h |
|---|---|
| Air throw | 38 m |
| External surface | 95.2 m² |
| Inner volume | 39.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 223 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-180GE10-C01 C | None |
|---|---|
| EA-180GE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.38 | 10.32 | 10.28 | 10.26 | 10.17 | 10.04 | 9.89 | 9.95 | 10.52 | 11.32 | 10.97 | 10.84 | 10.66 | 10.38 |
| 5 | 13.37 | 13.49 | 13.59 | 13.65 | 13.62 | 13.51 | 13.33 | 13.38 | 14.16 | 15.25 | 14.78 | 14.61 | 14.36 | 14.00 |
| 6 | 16.17 | 16.57 | 16.90 | 17.17 | 17.25 | 17.20 | 17.02 | 17.06 | 18.05 | 19.46 | 18.83 | 18.58 | 18.24 | 17.72 |
| 7 | 18.79 | 19.52 | 20.04 | 20.56 | 20.83 | 20.90 | 20.81 | 20.88 | 22.10 | 23.85 | 23.08 | 22.79 | 22.36 | 21.66 |
| 8 | 21.01 | 22.08 | 23.00 | 23.81 | 24.33 | 24.63 | 24.66 | 24.79 | 26.26 | 28.40 | 27.54 | 27.20 | 26.69 | 25.83 |
| 9 | 23.09 | 24.45 | 25.68 | 26.75 | 27.48 | 27.92 | 28.14 | 28.42 | 30.17 | 32.74 | 31.96 | 31.63 | 31.09 | 30.10 |
| 10 | 24.96 | 26.68 | 28.25 | 29.62 | 30.57 | 31.18 | 31.51 | 31.87 | 33.85 | 36.74 | 35.91 | 35.53 | 34.97 | 34.01 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.85 | 8.74 | 8.68 | 8.65 | 8.58 | 8.48 | 8.36 | 8.47 | 8.99 | 9.70 | 9.44 | 9.34 | 9.20 | 8.99 |
| 5 | 11.35 | 11.34 | 11.37 | 11.40 | 11.35 | 11.25 | 11.09 | 11.18 | 11.85 | 12.79 | 12.41 | 12.28 | 12.10 | 11.82 |
| 6 | 13.84 | 14.00 | 14.14 | 14.28 | 14.27 | 14.18 | 14.02 | 14.08 | 14.90 | 16.08 | 15.56 | 15.37 | 15.10 | 14.68 |
| 7 | 16.18 | 16.55 | 16.88 | 17.16 | 17.27 | 17.23 | 17.07 | 17.12 | 18.11 | 19.55 | 18.89 | 18.64 | 18.28 | 17.68 |
| 8 | 18.37 | 19.01 | 19.57 | 19.96 | 20.20 | 20.26 | 20.16 | 20.23 | 21.40 | 23.12 | 22.35 | 22.04 | 21.59 | 20.86 |
| 9 | 20.40 | 21.23 | 22.04 | 22.75 | 23.15 | 23.33 | 23.30 | 23.40 | 24.77 | 26.76 | 25.93 | 25.57 | 25.05 | 24.18 |
| 10 | 22.11 | 23.27 | 24.33 | 25.25 | 25.84 | 26.19 | 26.33 | 26.57 | 28.17 | 30.45 | 29.55 | 29.16 | 28.57 | 27.57 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 35.905 | 29.553 |
| SC2 | 0 | 8 | 24.793 | 20.227 |
| SC3 | -18 | 7 | 20.691 | 17.225 |
| SC4 | -25 | 6 | 16.904 | 14.144 |
| SC5 | -34 | 6 | 16.283 | 13.895 |
| A | 1715 mm |
|---|---|
| B | 1050 mm |
| C | 1430 mm |
| F | 1010 mm |
| G | 1100 mm |
| E | 1335 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 1715 mm |
|---|---|
| Width | 1100 mm |
| Height | 1430 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.