EA-130BE6-C01 C
3.23 kW
Defrost: None
Product code: EA-230AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,691 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 9.3 m² |
| Inner volume | 4.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 33 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 67.2 dB(A) |
| Energy class | B |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EA-230AC10-C01 C | None |
|---|---|
| EA-230AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.28 | 1.28 | 1.27 | 1.27 | 1.26 | 1.24 | 1.22 | 1.24 | 1.31 | 1.41 | 1.36 | 1.35 | 1.32 | 1.29 |
| 5 | 1.66 | 1.68 | 1.69 | 1.71 | 1.71 | 1.70 | 1.68 | 1.69 | 1.79 | 1.93 | 1.87 | 1.85 | 1.82 | 1.78 |
| 6 | 2.02 | 2.07 | 2.12 | 2.16 | 2.18 | 2.18 | 2.16 | 2.18 | 2.30 | 2.49 | 2.41 | 2.38 | 2.34 | 2.27 |
| 7 | 2.38 | 2.47 | 2.55 | 2.62 | 2.65 | 2.67 | 2.67 | 2.68 | 2.84 | 3.08 | 2.98 | 2.95 | 2.89 | 2.81 |
| 8 | 2.70 | 2.82 | 2.94 | 3.05 | 3.12 | 3.17 | 3.18 | 3.20 | 3.40 | 3.68 | 3.58 | 3.54 | 3.47 | 3.37 |
| 9 | 2.97 | 3.14 | 3.30 | 3.44 | 3.52 | 3.59 | 3.63 | 3.68 | 3.91 | 4.25 | 4.16 | 4.12 | 4.06 | 3.95 |
| 10 | 3.22 | 3.44 | 3.62 | 3.80 | 3.92 | 4.01 | 4.07 | 4.13 | 4.39 | 4.78 | 4.68 | 4.64 | 4.58 | 4.47 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.684 |
| SC2 | 0 | 8 | 3.204 |
| SC3 | -18 | 7 | 2.636 |
| SC4 | -25 | 6 | 2.119 |
| SC5 | -34 | 6 | 2.035 |
| A | 1157 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 418 mm |
| E | 835 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 1157 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.