EA-135AG8-C01 C
4.41 kW
Defrost: None
Product code: EA-230BC6-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,469 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 18.1 m² |
| Inner volume | 4.8 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 33 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-230BC6-C05 C | None |
|---|---|
| EA-230BC6-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.88 | 1.85 | 1.83 | 1.83 | 1.81 | 1.79 | 1.77 | 1.80 | 1.91 | 2.06 | 2.01 | 1.99 | 1.97 | 1.93 |
| 5 | 2.44 | 2.43 | 2.43 | 2.43 | 2.42 | 2.40 | 2.37 | 2.39 | 2.53 | 2.73 | 2.65 | 2.63 | 2.59 | 2.54 |
| 6 | 2.99 | 3.01 | 3.04 | 3.07 | 3.07 | 3.05 | 3.02 | 3.03 | 3.21 | 3.46 | 3.35 | 3.31 | 3.25 | 3.17 |
| 7 | 3.54 | 3.60 | 3.66 | 3.71 | 3.74 | 3.73 | 3.70 | 3.71 | 3.93 | 4.24 | 4.10 | 4.04 | 3.97 | 3.84 |
| 8 | 4.04 | 4.16 | 4.27 | 4.37 | 4.42 | 4.43 | 4.40 | 4.42 | 4.68 | 5.05 | 4.89 | 4.82 | 4.73 | 4.57 |
| 9 | 4.48 | 4.65 | 4.80 | 4.94 | 5.03 | 5.08 | 5.09 | 5.13 | 5.44 | 5.87 | 5.70 | 5.62 | 5.51 | 5.32 |
| 10 | 4.89 | 5.12 | 5.32 | 5.48 | 5.60 | 5.68 | 5.71 | 5.76 | 6.11 | 6.62 | 6.46 | 6.39 | 6.28 | 6.09 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.463 |
| SC2 | 0 | 8 | 4.418 |
| SC3 | -18 | 7 | 3.725 |
| SC4 | -25 | 6 | 3.039 |
| SC5 | -34 | 6 | 2.997 |
| A | 1357 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1357 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.