EA-163ED10-C06 C
9.78 kW
Defrost: None
Product code: EA-240AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,084 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 26.9 m² |
| Inner volume | 12.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 69 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-240AE10-C01 C | None |
|---|---|
| EA-240AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.03 | 4.00 | 3.99 | 3.98 | 3.95 | 3.89 | 3.82 | 3.88 | 4.11 | 4.43 | 4.30 | 4.24 | 4.17 | 4.06 |
| 5 | 5.19 | 5.24 | 5.29 | 5.33 | 5.33 | 5.28 | 5.20 | 5.26 | 5.57 | 6.01 | 5.82 | 5.75 | 5.66 | 5.52 |
| 6 | 6.34 | 6.46 | 6.59 | 6.71 | 6.76 | 6.74 | 6.67 | 6.73 | 7.12 | 7.69 | 7.42 | 7.33 | 7.19 | 6.96 |
| 7 | 7.40 | 7.66 | 7.90 | 8.10 | 8.21 | 8.23 | 8.19 | 8.25 | 8.73 | 9.44 | 9.12 | 8.99 | 8.81 | 8.50 |
| 8 | 8.36 | 8.73 | 9.08 | 9.39 | 9.59 | 9.71 | 9.72 | 9.79 | 10.36 | 11.22 | 10.87 | 10.72 | 10.50 | 10.12 |
| 9 | 9.21 | 9.71 | 10.17 | 10.54 | 10.81 | 10.98 | 11.05 | 11.19 | 11.88 | 12.89 | 12.57 | 12.43 | 12.21 | 11.78 |
| 10 | 9.99 | 10.63 | 11.16 | 11.67 | 12.04 | 12.27 | 12.38 | 12.56 | 13.33 | 14.47 | 14.13 | 13.97 | 13.72 | 13.29 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.126 |
| SC2 | 0 | 8 | 9.786 |
| SC3 | -18 | 7 | 8.156 |
| SC4 | -25 | 6 | 6.593 |
| SC5 | -34 | 6 | 6.382 |
| A | 1467 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1467 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.