EA-335AE8-C01 C
11.81 kW
Defrost: None
Product code: EA-240AE6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,572 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 42.2 m² |
| Inner volume | 12.6 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 70 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-240AE6-C01 C | None |
|---|---|
| EA-240AE6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.03 | 5.00 | 5.00 | 5.00 | 4.97 | 4.92 | 4.84 | 4.95 | 5.27 | 5.71 | 5.57 | 5.53 | 5.48 | 5.37 |
| 5 | 6.43 | 6.49 | 6.55 | 6.60 | 6.60 | 6.54 | 6.45 | 6.54 | 6.94 | 7.50 | 7.27 | 7.20 | 7.09 | 6.95 |
| 6 | 7.83 | 7.99 | 8.14 | 8.25 | 8.29 | 8.26 | 8.17 | 8.24 | 8.72 | 9.42 | 9.10 | 8.98 | 8.80 | 8.53 |
| 7 | 9.12 | 9.42 | 9.69 | 9.92 | 10.03 | 10.04 | 9.94 | 10.01 | 10.59 | 11.45 | 11.04 | 10.89 | 10.65 | 10.27 |
| 8 | 10.25 | 10.68 | 11.07 | 11.42 | 11.63 | 11.72 | 11.70 | 11.81 | 12.51 | 13.51 | 13.05 | 12.86 | 12.57 | 12.09 |
| 9 | 11.29 | 11.87 | 12.40 | 12.81 | 13.09 | 13.25 | 13.28 | 13.42 | 14.23 | 15.41 | 14.99 | 14.79 | 14.50 | 13.97 |
| 10 | 12.25 | 12.92 | 13.61 | 14.20 | 14.58 | 14.80 | 14.87 | 15.04 | 15.94 | 17.26 | 16.80 | 16.58 | 16.24 | 15.67 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.797 |
| SC2 | 0 | 8 | 11.813 |
| SC3 | -18 | 7 | 9.977 |
| SC4 | -25 | 6 | 8.140 |
| SC5 | -34 | 6 | 7.876 |
| A | 1467 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E | 1135 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 1467 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.