EA-163EE10-C11 C
16.02 kW
Defrost: None
Product code: EA-245AC4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,957 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 53.3 m² |
| Inner volume | 11.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 81 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| EA-245AC4-C01 C | None |
|---|---|
| EA-245AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.54 | 6.70 | 6.79 | 6.89 | 6.90 | 6.86 | 6.77 | 6.88 | 7.31 | 7.88 | 7.65 | 7.57 | 7.44 | 7.26 |
| 5 | 8.23 | 8.58 | 8.89 | 9.15 | 9.31 | 9.37 | 9.30 | 9.39 | 9.97 | 10.77 | 10.46 | 10.35 | 10.20 | 9.97 |
| 6 | 9.61 | 10.16 | 10.58 | 11.00 | 11.27 | 11.43 | 11.48 | 11.67 | 12.40 | 13.47 | 13.16 | 13.05 | 12.87 | 12.61 |
| 7 | 10.88 | 11.56 | 12.25 | 12.85 | 13.26 | 13.51 | 13.62 | 13.84 | 14.71 | 15.98 | 15.61 | 15.47 | 15.24 | 14.88 |
| 8 | ≈ 11.93 | 12.92 | 13.83 | 14.64 | 15.21 | 15.58 | 15.77 | 16.04 | 17.06 | 18.55 | 18.12 | 17.94 | 17.67 | 17.22 |
| 9 | ≈ 12.94 | 14.17 | 15.32 | 16.35 | 17.12 | 17.63 | 17.92 | 18.25 | 19.42 | 21.13 | 20.67 | 20.46 | 20.15 | 19.61 |
| 10 | ≈ 13.84 | 15.31 | 16.72 | 17.99 | 18.95 | 19.63 | 20.05 | 20.47 | 21.79 | 23.72 | 23.24 | 23.01 | 22.66 | 22.04 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 23.243 |
| SC2 | 0 | 8 | 16.040 |
| SC3 | -18 | 7 | 13.032 |
| SC4 | -25 | 6 | 10.583 |
| SC5 | -34 | 6 | 9.743 |
| A | 1767 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 1767 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.