EA-150AG8-C09 C
11.68 kW
Defrost: None
Product code: EA-245AC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 10,856 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 29.7 m² |
| Inner volume | 11.4 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 78 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-245AC8-C01 C | None |
|---|---|
| EA-245AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.63 | 4.59 | 4.56 | 4.53 | 4.47 | 4.39 | 4.30 | 4.30 | 4.53 | 4.86 | 4.68 | 4.62 | 4.53 | 4.40 |
| 5 | 6.07 | 6.14 | 6.19 | 6.23 | 6.21 | 6.14 | 6.04 | 6.05 | 6.40 | 6.88 | 6.64 | 6.56 | 6.44 | 6.24 |
| 6 | 7.48 | 7.69 | 7.87 | 8.01 | 8.06 | 8.03 | 7.95 | 7.98 | 8.45 | 9.10 | 8.78 | 8.67 | 8.51 | 8.26 |
| 7 | 8.68 | 9.02 | 9.34 | 9.62 | 9.80 | 9.90 | 9.91 | 9.99 | 10.58 | 11.43 | 11.07 | 10.93 | 10.73 | 10.40 |
| 8 | 9.75 | 10.24 | 10.64 | 11.04 | 11.30 | 11.47 | 11.55 | 11.69 | 12.41 | 13.48 | 13.17 | 13.05 | 12.86 | 12.56 |
| 9 | 10.73 | 11.33 | 11.92 | 12.45 | 12.83 | 13.07 | 13.20 | 13.37 | 14.21 | 15.44 | 15.10 | 14.96 | 14.75 | 14.39 |
| 10 | 11.53 | 12.40 | 13.16 | 13.84 | 14.32 | 14.65 | 14.85 | 15.07 | 16.02 | 17.42 | 17.06 | 16.90 | 16.67 | 16.26 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.061 |
| SC2 | 0 | 8 | 11.686 |
| SC3 | -18 | 7 | 9.702 |
| SC4 | -25 | 6 | 7.868 |
| SC5 | -34 | 6 | 7.534 |
| A | 1767 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1767 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.