EA-340AG4-C01 C
19.27 kW
Defrost: None
Product code: EA-250AE10-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,381 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 47.5 m² |
| Inner volume | 22.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 112 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,420 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-250AE10-C09 C | None |
|---|---|
| EA-250AE10-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.85 | 7.71 | 7.61 | 7.54 | 7.42 | 7.28 | 7.13 | 7.17 | 7.56 | 8.12 | 7.84 | 7.74 | 7.59 | 7.38 |
| 5 | 10.30 | 10.27 | 10.27 | 10.27 | 10.20 | 10.06 | 9.87 | 9.90 | 10.47 | 11.26 | 10.87 | 10.74 | 10.55 | 10.27 |
| 6 | 12.74 | 12.83 | 12.99 | 13.12 | 13.12 | 13.03 | 12.86 | 12.89 | 13.63 | 14.67 | 14.15 | 13.96 | 13.68 | 13.28 |
| 7 | 15.02 | 15.38 | 15.71 | 16.01 | 16.13 | 16.10 | 15.97 | 16.02 | 16.94 | 18.27 | 17.63 | 17.38 | 17.02 | 16.45 |
| 8 | 17.06 | 17.64 | 18.19 | 18.69 | 19.02 | 19.19 | 19.15 | 19.23 | 20.36 | 21.97 | 21.27 | 20.98 | 20.56 | 19.86 |
| 9 | 18.89 | 19.71 | 20.47 | 21.08 | 21.54 | 21.81 | 21.93 | 22.14 | 23.50 | 25.49 | 24.87 | 24.60 | 24.18 | 23.37 |
| 10 | 20.60 | 21.69 | 22.58 | 23.47 | 24.06 | 24.44 | 24.64 | 24.92 | 26.45 | 28.70 | 28.04 | 27.74 | 27.29 | 26.52 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 28.035 |
| SC2 | 0 | 8 | 19.229 |
| SC3 | -18 | 7 | 16.074 |
| SC4 | -25 | 6 | 12.985 |
| SC5 | -34 | 6 | 12.788 |
| A | 2087 mm |
|---|---|
| B | 640 mm |
| C | 685 mm |
| F | 445 mm |
| E1 | 868 mm |
| E | 1735 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2087 mm |
|---|---|
| Width | 640 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.