EA-245AG6-C01 C
20.36 kW
Defrost: None
Product code: EA-250AE8-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 13,008 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 57.6 m² |
| Inner volume | 22.3 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 114 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,420 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-250AE8-C09 C | None |
|---|---|
| EA-250AE8-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.32 | 8.20 | 8.12 | 8.05 | 7.95 | 7.81 | 7.66 | 7.74 | 8.18 | 8.79 | 8.51 | 8.41 | 8.26 | 8.04 |
| 5 | 10.88 | 10.89 | 10.92 | 10.94 | 10.87 | 10.74 | 10.55 | 10.61 | 11.23 | 12.10 | 11.70 | 11.56 | 11.37 | 11.08 |
| 6 | 13.43 | 13.63 | 13.78 | 13.94 | 13.97 | 13.88 | 13.70 | 13.75 | 14.54 | 15.66 | 15.11 | 14.91 | 14.62 | 14.20 |
| 7 | 15.78 | 16.24 | 16.65 | 16.99 | 17.15 | 17.12 | 16.99 | 17.05 | 18.04 | 19.45 | 18.78 | 18.52 | 18.14 | 17.53 |
| 8 | 17.81 | 18.49 | 19.12 | 19.68 | 20.04 | 20.17 | 20.22 | 20.41 | 21.63 | 23.37 | 22.61 | 22.31 | 21.85 | 21.11 |
| 9 | 19.69 | 20.63 | 21.39 | 22.16 | 22.67 | 22.96 | 23.07 | 23.31 | 24.73 | 26.82 | 26.15 | 25.87 | 25.43 | 24.72 |
| 10 | 21.43 | 22.56 | 23.67 | 24.65 | 25.31 | 25.72 | 25.92 | 26.22 | 27.83 | 30.19 | 29.47 | 29.15 | 28.66 | 27.84 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 29.471 |
| SC2 | 0 | 8 | 20.413 |
| SC3 | -18 | 7 | 17.075 |
| SC4 | -25 | 6 | 13.776 |
| SC5 | -34 | 6 | 13.486 |
| A | 2087 mm |
|---|---|
| B | 640 mm |
| C | 685 mm |
| F | 445 mm |
| E1 | 868 mm |
| E | 1735 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2087 mm |
|---|---|
| Width | 640 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.