EA-345AE8-C01 C
23.14 kW
Defrost: None
Product code: EA-250AG10-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 12,367 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 63.3 m² |
| Inner volume | 30.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 140 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 1,420 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-250AG10-C09 C | None |
|---|---|
| EA-250AG10-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.85 | 9.68 | 9.58 | 9.51 | 9.39 | 9.23 | 9.06 | 9.17 | 9.73 | 10.49 | 10.18 | 10.06 | 9.89 | 9.64 |
| 5 | 12.81 | 12.75 | 12.75 | 12.75 | 12.67 | 12.51 | 12.29 | 12.38 | 13.11 | 14.13 | 13.65 | 13.49 | 13.27 | 12.96 |
| 6 | 15.68 | 15.82 | 15.97 | 16.11 | 16.10 | 15.98 | 15.77 | 15.82 | 16.73 | 18.04 | 17.39 | 17.15 | 16.81 | 16.28 |
| 7 | 18.53 | 18.88 | 19.21 | 19.48 | 19.60 | 19.56 | 19.37 | 19.42 | 20.54 | 22.16 | 21.36 | 21.04 | 20.58 | 19.83 |
| 8 | 21.15 | 21.77 | 22.36 | 22.87 | 23.13 | 23.19 | 23.03 | 23.12 | 24.45 | 26.39 | 25.50 | 25.13 | 24.57 | 23.63 |
| 9 | 23.47 | 24.34 | 25.17 | 25.92 | 26.38 | 26.63 | 26.68 | 26.83 | 28.40 | 30.66 | 29.70 | 29.28 | 28.62 | 27.52 |
| 10 | 25.62 | 26.79 | 27.88 | 28.73 | 29.37 | 29.75 | 29.88 | 30.18 | 32.00 | 34.66 | 33.78 | 33.36 | 32.72 | 31.48 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 33.778 |
| SC2 | 0 | 8 | 23.115 |
| SC3 | -18 | 7 | 19.550 |
| SC4 | -25 | 6 | 15.967 |
| SC5 | -34 | 6 | 15.734 |
| A | 2087 mm |
|---|---|
| B | 740 mm |
| C | 685 mm |
| F | 545 mm |
| E1 | 868 mm |
| E | 1735 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2087 mm |
|---|---|
| Width | 690 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.