EA-163GC4-C13 C
23.19 kW
Defrost: None
Product code: EA-263EE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 16,641 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 97.7 m² |
| Inner volume | 41.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 201 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 77.1 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-263EE10-C01 C | None |
|---|---|
| EA-263EE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.15 | 10.00 | 9.91 | 9.86 | 9.77 | 9.65 | 9.52 | 9.60 | 10.18 | 10.98 | 10.68 | 10.56 | 10.40 | 10.15 |
| 5 | 13.11 | 13.02 | 13.02 | 13.04 | 12.97 | 12.84 | 12.67 | 12.73 | 13.48 | 14.54 | 14.10 | 13.94 | 13.73 | 13.41 |
| 6 | 15.95 | 16.09 | 16.23 | 16.36 | 16.34 | 16.24 | 16.05 | 16.09 | 17.02 | 18.35 | 17.76 | 17.54 | 17.22 | 16.74 |
| 7 | 18.67 | 19.05 | 19.40 | 19.70 | 19.80 | 19.76 | 19.59 | 19.61 | 20.74 | 22.35 | 21.62 | 21.34 | 20.92 | 20.26 |
| 8 | 21.22 | 21.90 | 22.41 | 22.93 | 23.19 | 23.26 | 23.16 | 23.21 | 24.55 | 26.51 | 25.65 | 25.30 | 24.79 | 23.96 |
| 9 | 23.57 | 24.43 | 25.30 | 26.08 | 26.58 | 26.80 | 26.78 | 26.87 | 28.45 | 30.74 | 29.80 | 29.40 | 28.81 | 27.82 |
| 10 | 25.54 | 26.80 | 27.95 | 28.96 | 29.61 | 30.00 | 30.17 | 30.43 | 32.28 | 34.98 | 34.00 | 33.55 | 32.88 | 31.76 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 33.997 |
| SC2 | 0 | 8 | 23.205 |
| SC3 | -18 | 7 | 19.760 |
| SC4 | -25 | 6 | 16.229 |
| SC5 | -34 | 6 | 16.003 |
| A | 2015 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2015 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.