EA-263FD10-C13 C
31.31 kW
Defrost: None
Product code: EA-263EG7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 14,634 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 179.9 m² |
| Inner volume | 53.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 234 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.2 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-263EG7-C01 C | None |
|---|---|
| EA-263EG7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.01 | 13.93 | 13.92 | 13.95 | 13.90 | 13.80 | 13.65 | 13.90 | 14.78 | 16.02 | 15.65 | 15.53 | 15.37 | 15.14 |
| 5 | 17.78 | 17.85 | 17.92 | 18.06 | 18.05 | 17.94 | 17.75 | 17.95 | 19.04 | 20.60 | 20.02 | 19.81 | 19.52 | 19.09 |
| 6 | 21.37 | 21.70 | 22.02 | 22.30 | 22.39 | 22.29 | 22.07 | 22.22 | 23.54 | 25.45 | 24.65 | 24.34 | 23.91 | 23.21 |
| 7 | 24.79 | 25.45 | 26.04 | 26.55 | 26.78 | 26.72 | 26.52 | 26.65 | 28.19 | 30.48 | 29.47 | 29.08 | 28.49 | 27.54 |
| 8 | 27.99 | 29.04 | 29.84 | 30.63 | 31.07 | 31.18 | 31.04 | 31.19 | 33.01 | 35.65 | 34.50 | 34.02 | 33.30 | 32.11 |
| 9 | 30.73 | 32.19 | 33.46 | 34.59 | 35.27 | 35.64 | 35.59 | 35.80 | 37.89 | 40.93 | 39.65 | 39.09 | 38.24 | 36.82 |
| 10 | 33.38 | 35.20 | 36.85 | 38.29 | 39.20 | 39.71 | 39.86 | 40.22 | 42.64 | 46.14 | 44.86 | 44.22 | 43.26 | 41.61 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 44.856 |
| SC2 | 0 | 8 | 31.189 |
| SC3 | -18 | 7 | 26.672 |
| SC4 | -25 | 6 | 22.016 |
| SC5 | -34 | 6 | 21.472 |
| A | 2015 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2015 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.