EA-150AC8-C09 C
7.56 kW
Defrost: None
Product code: EA-330AE4-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 2,803 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 49.5 m² |
| Inner volume | 10.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 49 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-330AE4-C05 C | None |
|---|---|
| EA-330AE4-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.41 | 3.42 | 3.44 | 3.47 | 3.47 | 3.46 | 3.43 | 3.51 | 3.73 | 4.06 | 3.97 | 3.94 | 3.90 | 3.85 |
| 5 | 4.26 | 4.32 | 4.38 | 4.44 | 4.46 | 4.45 | 4.41 | 4.47 | 4.74 | 5.14 | 4.99 | 4.94 | 4.86 | 4.74 |
| 6 | 5.08 | 5.20 | 5.32 | 5.43 | 5.47 | 5.47 | 5.43 | 5.48 | 5.81 | 6.29 | 6.08 | 6.00 | 5.88 | 5.68 |
| 7 | 5.89 | 6.09 | 6.27 | 6.42 | 6.49 | 6.52 | 6.48 | 6.52 | 6.90 | 7.46 | 7.22 | 7.11 | 6.96 | 6.70 |
| 8 | 6.62 | 6.91 | 7.17 | 7.39 | 7.53 | 7.57 | 7.53 | 7.59 | 8.03 | 8.67 | 8.39 | 8.26 | 8.07 | 7.75 |
| 9 | 7.28 | 7.65 | 7.99 | 8.29 | 8.48 | 8.54 | 8.56 | 8.64 | 9.15 | 9.88 | 9.57 | 9.42 | 9.20 | 8.82 |
| 10 | 7.88 | 8.35 | 8.79 | 9.12 | 9.36 | 9.50 | 9.54 | 9.63 | 10.20 | 11.03 | 10.72 | 10.57 | 10.34 | 9.91 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.718 |
| SC2 | 0 | 8 | 7.585 |
| SC3 | -18 | 7 | 6.463 |
| SC4 | -25 | 6 | 5.321 |
| SC5 | -34 | 6 | 5.114 |
| A | 1657 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 4505 mm |
| E2 | 434 mm |
| E | 1335 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1657 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.