EA-163FC10-C19 C
10.87 kW
Defrost: None
Product code: EA-335AC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 7,219 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 32.9 m² |
| Inner volume | 9.8 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 67 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-335AC6-C01 C | None |
|---|---|
| EA-335AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.48 | 4.42 | 4.39 | 4.36 | 4.32 | 4.26 | 4.19 | 4.24 | 4.49 | 4.83 | 4.69 | 4.64 | 4.57 | 4.46 |
| 5 | 5.84 | 5.86 | 5.88 | 5.90 | 5.87 | 5.81 | 5.72 | 5.77 | 6.11 | 6.59 | 6.39 | 6.32 | 6.23 | 6.09 |
| 6 | 7.21 | 7.33 | 7.44 | 7.53 | 7.53 | 7.49 | 7.40 | 7.45 | 7.88 | 8.50 | 8.22 | 8.11 | 7.97 | 7.76 |
| 7 | 8.43 | 8.67 | 8.90 | 9.11 | 9.23 | 9.25 | 9.18 | 9.22 | 9.76 | 10.54 | 10.19 | 10.05 | 9.85 | 9.54 |
| 8 | 9.50 | 9.86 | 10.20 | 10.46 | 10.65 | 10.75 | 10.78 | 10.89 | 11.56 | 12.54 | 12.21 | 12.08 | 11.85 | 11.46 |
| 9 | 10.49 | 10.94 | 11.41 | 11.82 | 12.09 | 12.24 | 12.30 | 12.43 | 13.19 | 14.31 | 13.95 | 13.80 | 13.58 | 13.20 |
| 10 | 11.42 | 12.03 | 12.62 | 13.15 | 13.50 | 13.72 | 13.82 | 13.99 | 14.85 | 16.10 | 15.72 | 15.55 | 15.29 | 14.85 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 15.718 |
| SC2 | 0 | 8 | 10.890 |
| SC3 | -18 | 7 | 9.167 |
| SC4 | -25 | 6 | 7.436 |
| SC5 | -34 | 6 | 7.243 |
| A | 1857 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 5175 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1857 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.