EA-150AE4-C10 C
12.67 kW
Defrost: None
Product code: EA-335AE7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 6,494 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 42.9 m² |
| Inner volume | 14.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 78 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-335AE7-C01 C | None |
|---|---|
| EA-335AE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.23 | 5.34 | 5.44 | 5.52 | 5.53 | 5.50 | 5.44 | 5.55 | 5.90 | 6.39 | 6.23 | 6.18 | 6.11 | 6.00 |
| 5 | 6.60 | 6.84 | 7.06 | 7.22 | 7.31 | 7.32 | 7.27 | 7.38 | 7.83 | 8.47 | 8.22 | 8.12 | 7.99 | 7.80 |
| 6 | 7.82 | 8.24 | 8.60 | 8.91 | 9.12 | 9.19 | 9.16 | 9.28 | 9.85 | 10.65 | 10.33 | 10.20 | 10.01 | 9.70 |
| 7 | 8.88 | 9.44 | 9.95 | 10.33 | 10.64 | 10.82 | 10.89 | 11.06 | 11.75 | 12.77 | 12.45 | 12.31 | 12.11 | 11.73 |
| 8 | 9.82 | 10.56 | 11.15 | 11.74 | 12.16 | 12.41 | 12.54 | 12.75 | 13.55 | 14.72 | 14.37 | 14.21 | 13.97 | 13.55 |
| 9 | ≈ 10.68 | 11.52 | 12.36 | 13.10 | 13.64 | 13.99 | 14.19 | 14.44 | 15.35 | 16.68 | 16.30 | 16.12 | 15.85 | 15.36 |
| 10 | ≈ 11.45 | 12.47 | 13.49 | 14.39 | 15.08 | 15.55 | 15.82 | 16.13 | 17.15 | 18.65 | 18.25 | 18.06 | 17.75 | 17.19 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.254 |
| SC2 | 0 | 8 | 12.746 |
| SC3 | -18 | 7 | 10.469 |
| SC4 | -25 | 6 | 8.597 |
| SC5 | -34 | 6 | 7.922 |
| A | 1857 mm |
|---|---|
| B | 573 mm |
| C | 525 mm |
| F | 395 mm |
| E1 | 5175 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1857 mm |
|---|---|
| Width | 573 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.