EA-263ED10-C06 C
20.19 kW
Defrost: None
Product code: EA-345AC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 15,749 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 57.5 m² |
| Inner volume | 17.3 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 111 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-345AC6-C01 C | None |
|---|---|
| EA-345AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.19 | 8.11 | 8.05 | 7.99 | 7.90 | 7.77 | 7.63 | 7.68 | 8.10 | 8.71 | 8.43 | 8.33 | 8.19 | 7.97 |
| 5 | 10.79 | 10.83 | 10.91 | 10.96 | 10.91 | 10.79 | 10.61 | 10.67 | 11.29 | 12.15 | 11.76 | 11.63 | 11.44 | 11.14 |
| 6 | 13.24 | 13.57 | 13.85 | 14.08 | 14.14 | 14.07 | 13.91 | 13.97 | 14.79 | 15.93 | 15.39 | 15.19 | 14.92 | 14.51 |
| 7 | 15.28 | 15.82 | 16.32 | 16.77 | 16.98 | 17.12 | 17.16 | 17.34 | 18.41 | 19.95 | 19.31 | 19.07 | 18.71 | 18.15 |
| 8 | 17.18 | 17.98 | 18.61 | 19.25 | 19.66 | 19.90 | 19.99 | 20.21 | 21.46 | 23.28 | 22.72 | 22.49 | 22.16 | 21.62 |
| 9 | 18.93 | 19.91 | 20.89 | 21.74 | 22.33 | 22.68 | 22.86 | 23.12 | 24.55 | 26.66 | 26.03 | 25.77 | 25.38 | 24.74 |
| 10 | 20.45 | 21.82 | 23.07 | 24.18 | 24.96 | 25.46 | 25.73 | 26.06 | 27.68 | 30.06 | 29.39 | 29.10 | 28.66 | 27.92 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 29.393 |
| SC2 | 0 | 8 | 20.209 |
| SC3 | -18 | 7 | 16.892 |
| SC4 | -25 | 6 | 13.852 |
| SC5 | -34 | 6 | 13.328 |
| A | 2467 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2135 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 2467 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.