EA-250AG7-C09 C
26.16 kW
Defrost: None
Product code: EA-345AE7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 14,288 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 75.1 m² |
| Inner volume | 26.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 130 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø54 |
| EA-345AE7-C01 C | None |
|---|---|
| EA-345AE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.94 | 10.80 | 10.71 | 10.64 | 10.52 | 10.35 | 10.16 | 10.33 | 10.96 | 11.81 | 11.46 | 11.33 | 11.15 | 10.87 |
| 5 | 14.22 | 14.25 | 14.30 | 14.34 | 14.25 | 14.08 | 13.83 | 13.97 | 14.80 | 15.96 | 15.44 | 15.27 | 15.04 | 14.69 |
| 6 | 17.48 | 17.75 | 17.99 | 18.16 | 18.19 | 18.06 | 17.81 | 17.91 | 18.95 | 20.43 | 19.69 | 19.42 | 19.04 | 18.46 |
| 7 | 20.47 | 21.02 | 21.55 | 22.04 | 22.23 | 22.19 | 21.96 | 22.06 | 23.33 | 25.17 | 24.27 | 23.91 | 23.39 | 22.57 |
| 8 | 23.06 | 23.90 | 24.68 | 25.38 | 25.72 | 25.93 | 25.93 | 26.16 | 27.74 | 30.06 | 29.02 | 28.60 | 27.97 | 26.93 |
| 9 | 25.48 | 26.66 | 27.61 | 28.56 | 29.13 | 29.46 | 29.53 | 29.82 | 31.62 | 34.25 | 33.32 | 32.91 | 32.30 | 31.27 |
| 10 | 27.73 | 29.14 | 30.53 | 31.75 | 32.53 | 32.99 | 33.15 | 33.51 | 35.54 | 38.49 | 37.48 | 37.02 | 36.32 | 35.13 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 37.478 |
| SC2 | 0 | 8 | 26.160 |
| SC3 | -18 | 7 | 22.144 |
| SC4 | -25 | 6 | 17.990 |
| SC5 | -34 | 6 | 17.564 |
| A | 2467 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2135 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø54 |
| Length | 2467 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.