EA-263FD7-C19 C
29.91 kW
Defrost: None
Product code: EA-350AC4-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 19,908 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 103.5 m² |
| Inner volume | 23.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 144 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 2,130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-350AC4-C09 C | None |
|---|---|
| EA-350AC4-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.30 | 12.04 | 11.86 | 11.74 | 11.58 | 11.40 | 11.23 | 11.33 | 11.97 | 12.91 | 12.56 | 12.43 | 12.26 | 12.01 |
| 5 | 16.34 | 16.23 | 16.15 | 16.08 | 15.90 | 15.66 | 15.38 | 15.46 | 16.36 | 17.62 | 17.09 | 16.91 | 16.67 | 16.28 |
| 6 | 20.45 | 20.62 | 20.75 | 20.84 | 20.71 | 20.47 | 20.12 | 20.17 | 21.32 | 22.95 | 22.16 | 21.89 | 21.51 | 20.97 |
| 7 | 23.93 | 24.41 | 24.87 | 25.31 | 25.53 | 25.58 | 25.31 | 25.32 | 26.75 | 28.77 | 27.73 | 27.35 | 26.80 | 25.97 |
| 8 | 27.10 | 27.91 | 28.56 | 29.22 | 29.60 | 29.75 | 29.71 | 29.93 | 31.73 | 34.36 | 33.44 | 33.07 | 32.55 | 31.56 |
| 9 | 30.09 | 31.16 | 32.23 | 33.18 | 33.74 | 34.02 | 34.05 | 34.29 | 36.35 | 39.37 | 38.31 | 37.88 | 37.25 | 36.24 |
| 10 | 32.75 | 34.36 | 35.82 | 37.08 | 37.88 | 38.29 | 38.42 | 38.72 | 41.06 | 44.47 | 43.29 | 42.79 | 42.06 | 40.87 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 43.290 |
| SC2 | 0 | 8 | 29.927 |
| SC3 | -18 | 7 | 25.421 |
| SC4 | -25 | 6 | 20.747 |
| SC5 | -34 | 6 | 20.521 |
| A | 2937 mm |
|---|---|
| B | 590 mm |
| C | 715 mm |
| F | 510 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 2586 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2937 mm |
|---|---|
| Width | 590 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.