EA-263GC10-C19 C
26.54 kW
Defrost: None
Product code: EA-350AC6-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 20,812 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 74.5 m² |
| Inner volume | 23.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 139 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 2,130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.2 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-350AC6-C09 C | None |
|---|---|
| EA-350AC6-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.71 | 10.40 | 10.18 | 10.03 | 9.86 | 9.68 | 9.51 | 9.52 | 10.04 | 10.80 | 10.48 | 10.37 | 10.21 | 9.97 |
| 5 | 14.34 | 14.12 | 13.97 | 13.84 | 13.65 | 13.41 | 13.16 | 13.15 | 13.89 | 14.94 | 14.45 | 14.28 | 14.03 | 13.65 |
| 6 | 18.07 | 18.04 | 17.99 | 18.00 | 17.86 | 17.63 | 17.33 | 17.28 | 18.25 | 19.62 | 18.92 | 18.68 | 18.34 | 17.84 |
| 7 | 21.61 | 21.88 | 22.13 | 22.33 | 22.33 | 22.14 | 21.86 | 21.81 | 23.04 | 24.77 | 23.87 | 23.55 | 23.07 | 22.35 |
| 8 | 24.58 | 25.11 | 25.64 | 26.15 | 26.44 | 26.56 | 26.52 | 26.57 | 28.07 | 30.26 | 29.22 | 28.82 | 28.24 | 27.33 |
| 9 | 27.40 | 28.24 | 28.94 | 29.67 | 30.12 | 30.36 | 30.42 | 30.62 | 32.47 | 35.18 | 34.30 | 33.94 | 33.42 | 32.55 |
| 10 | 30.06 | 31.14 | 32.23 | 33.22 | 33.85 | 34.22 | 34.37 | 34.61 | 36.72 | 39.79 | 38.83 | 38.42 | 37.81 | 36.79 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 38.825 |
| SC2 | 0 | 8 | 26.568 |
| SC3 | -18 | 7 | 22.354 |
| SC4 | -25 | 6 | 17.993 |
| SC5 | -34 | 6 | 18.091 |
| A | 2937 mm |
|---|---|
| B | 590 mm |
| C | 715 mm |
| F | 510 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 2586 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2937 mm |
|---|---|
| Width | 590 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.