EA-263GD10-C13 C
36.96 kW
Defrost: None
Product code: EA-350BE7-C10 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 22,031 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 202.8 m² |
| Inner volume | 60.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 250 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 2,070 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-350BE7-C10 C | None |
|---|---|
| EA-350BE7-C10 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 16.48 | 16.23 | 16.12 | 16.08 | 16.00 | 15.89 | 15.76 | 15.84 | 16.80 | 18.16 | 17.74 | 17.58 | 17.35 | 17.00 |
| 5 | 21.16 | 20.97 | 20.97 | 21.02 | 20.96 | 20.84 | 20.67 | 20.71 | 21.93 | 23.69 | 23.06 | 22.83 | 22.51 | 22.02 |
| 6 | 25.72 | 25.83 | 26.00 | 26.20 | 26.19 | 26.10 | 25.92 | 25.93 | 27.44 | 29.63 | 28.79 | 28.48 | 28.02 | 27.33 |
| 7 | 30.11 | 30.57 | 31.02 | 31.45 | 31.61 | 31.59 | 31.43 | 31.42 | 33.25 | 35.88 | 34.84 | 34.44 | 33.86 | 32.93 |
| 8 | 34.28 | 35.17 | 35.85 | 36.57 | 36.96 | 37.09 | 37.02 | 37.05 | 39.22 | 42.39 | 41.16 | 40.68 | 39.97 | 38.83 |
| 9 | 37.94 | 39.27 | 40.49 | 41.62 | 42.35 | 42.66 | 42.71 | 42.82 | 45.35 | 49.04 | 47.69 | 47.14 | 46.32 | 44.97 |
| 10 | 41.37 | 43.14 | 44.76 | 46.23 | 47.18 | 47.79 | 48.11 | 48.46 | 51.42 | 55.75 | 54.32 | 53.71 | 52.78 | 51.25 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.55 | 14.29 | 14.18 | 14.16 | 14.10 | 14.02 | 13.92 | 14.04 | 14.90 | 16.14 | 15.78 | 15.66 | 15.48 | 15.22 |
| 5 | 18.56 | 18.38 | 18.32 | 18.35 | 18.30 | 18.20 | 18.06 | 18.14 | 19.23 | 20.80 | 20.27 | 20.08 | 19.81 | 19.40 |
| 6 | 22.64 | 22.58 | 22.60 | 22.73 | 22.73 | 22.63 | 22.47 | 22.52 | 23.84 | 25.77 | 25.05 | 24.78 | 24.40 | 23.81 |
| 7 | 26.56 | 26.73 | 26.97 | 27.24 | 27.31 | 27.24 | 27.08 | 27.10 | 28.68 | 30.99 | 30.09 | 29.75 | 29.24 | 28.44 |
| 8 | 30.33 | 30.81 | 31.29 | 31.75 | 31.96 | 31.98 | 31.84 | 31.85 | 33.70 | 36.39 | 35.33 | 34.90 | 34.28 | 33.27 |
| 9 | 33.91 | 34.75 | 35.44 | 36.15 | 36.53 | 36.67 | 36.61 | 36.67 | 38.82 | 41.94 | 40.74 | 40.24 | 39.51 | 38.31 |
| 10 | 37.28 | 38.37 | 39.51 | 40.57 | 41.15 | 41.43 | 41.46 | 41.59 | 44.03 | 47.59 | 46.28 | 45.72 | 44.89 | 43.49 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 54.322 | 46.277 |
| SC2 | 0 | 8 | 37.054 | 31.847 |
| SC3 | -18 | 7 | 31.538 | 27.286 |
| SC4 | -25 | 6 | 26.002 | 22.599 |
| SC5 | -34 | 6 | 25.779 | 22.652 |
| A | 3427 mm |
|---|---|
| B | 740 mm |
| C | 875 mm |
| F | 660 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 3035 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 3427 mm |
|---|---|
| Width | 740 mm |
| Height | 875 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.