EA-350AE10-C09 C
28.71 kW
Defrost: None
Product code: EA-363EC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 26,275 m³/h |
|---|---|
| Air throw | 24 m |
| External surface | 135.2 m² |
| Inner volume | 41.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 244 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 79.4 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-363EC7-C01 C | None |
|---|---|
| EA-363EC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.04 | 11.94 | 11.90 | 11.89 | 11.82 | 11.71 | 11.59 | 11.69 | 12.36 | 13.34 | 12.99 | 12.86 | 12.67 | 12.40 |
| 5 | 15.51 | 15.60 | 15.69 | 15.78 | 15.73 | 15.62 | 15.47 | 15.55 | 16.47 | 17.78 | 17.29 | 17.12 | 16.87 | 16.50 |
| 6 | 18.82 | 19.19 | 19.52 | 19.80 | 19.88 | 19.83 | 19.67 | 19.71 | 20.87 | 22.53 | 21.87 | 21.63 | 21.28 | 20.75 |
| 7 | 21.93 | 22.56 | 23.20 | 23.74 | 24.02 | 24.10 | 24.01 | 24.11 | 25.53 | 27.58 | 26.77 | 26.45 | 25.99 | 25.27 |
| 8 | 24.56 | 25.61 | 26.57 | 27.42 | 27.97 | 28.30 | 28.44 | 28.63 | 30.34 | 32.82 | 31.89 | 31.53 | 30.98 | 30.10 |
| 9 | 27.00 | 28.43 | 29.72 | 30.86 | 31.62 | 32.09 | 32.33 | 32.65 | 34.67 | 37.63 | 36.78 | 36.43 | 35.91 | 35.05 |
| 10 | 29.25 | 31.09 | 32.76 | 34.22 | 35.23 | 35.87 | 36.23 | 36.62 | 38.90 | 42.24 | 41.31 | 40.92 | 40.33 | 39.34 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 41.312 |
| SC2 | 0 | 8 | 28.632 |
| SC3 | -18 | 7 | 23.881 |
| SC4 | -25 | 6 | 19.523 |
| SC5 | -34 | 6 | 18.927 |
| A | 2815 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2815 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.