EA-363ED10-C11 C
41.00 kW
Defrost: None
Product code: EA-363EG10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 23,112 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 195.3 m² |
| Inner volume | 79.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 340 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 79.7 dB(A) |
| Energy class | B |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-363EG10-C01 C | None |
|---|---|
| EA-363EG10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 17.86 | 17.84 | 17.87 | 17.91 | 17.84 | 17.68 | 17.45 | 17.70 | 18.79 | 20.32 | 19.80 | 19.62 | 19.37 | 18.95 |
| 5 | 22.67 | 22.93 | 23.18 | 23.37 | 23.40 | 23.26 | 23.00 | 23.20 | 24.59 | 26.57 | 25.76 | 25.48 | 25.07 | 24.47 |
| 6 | 27.17 | 27.85 | 28.45 | 28.95 | 29.15 | 29.10 | 28.83 | 29.00 | 30.71 | 33.17 | 32.10 | 31.69 | 31.10 | 30.16 |
| 7 | 31.38 | 32.56 | 33.60 | 34.32 | 34.79 | 34.92 | 34.76 | 34.95 | 37.00 | 39.99 | 38.68 | 38.16 | 37.39 | 36.14 |
| 8 | 35.27 | 36.82 | 38.35 | 39.66 | 40.44 | 40.80 | 40.75 | 41.01 | 43.43 | 46.96 | 45.51 | 44.90 | 43.98 | 42.44 |
| 9 | 38.57 | 40.77 | 42.78 | 44.53 | 45.66 | 46.33 | 46.60 | 47.09 | 49.93 | 54.01 | 52.43 | 51.73 | 50.68 | 48.88 |
| 10 | 41.65 | 44.44 | 46.98 | 49.16 | 50.67 | 51.59 | 52.02 | 52.63 | 55.84 | 60.53 | 59.03 | 58.35 | 57.30 | 55.41 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 59.034 |
| SC2 | 0 | 8 | 41.012 |
| SC3 | -18 | 7 | 34.553 |
| SC4 | -25 | 6 | 28.449 |
| SC5 | -34 | 6 | 27.356 |
| A | 2815 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2815 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.