Skip to Content

Unit cooler EA-391AG10-C04 C

Unit cooler EA-391AG10-C04 C
Illustrative photo

Producer: Karyer · Line: EA (General)

Product code: EA-391AG10-C04 C

Cooling capacity i
141.01 kW
Air flow
85,045 m³/h
Fin spacing
10.0 mm
Air throw
53 m
Fans
3 × ⌀910 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Data

Evaporator
Air flow 85,045 m³/h
Air throw 53 m
External surface 586.0 m²
Inner volume 241.2 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 1,070 kg
Fans
Quantity 3
Diameter 910 mm
Speed 840 rpm
Power 8,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 71.0 dB(A)
Sound power 95.0 dB(A)
Energy class C
Connections
Inlet Ø54
Outlet Ø80
Defrost
EA-391AG10-C04 C None
EA-391AG10-C04 C ED Electric

Performance

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
141.014 kW
Low speed (Y)
114.245 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 62.27 61.25 60.64 60.30 59.71 58.97 58.14 58.46 61.94 66.83 64.97 64.27 63.26 61.72
5 80.37 79.69 79.60 79.65 79.20 78.40 77.36 77.50 82.01 88.41 85.68 84.71 83.34 81.31
6 97.81 98.42 99.12 99.81 99.62 98.98 97.90 97.90 103.53 111.59 107.95 106.60 104.65 101.63
7 114.48 116.51 118.40 120.06 120.61 120.31 119.33 119.11 125.96 135.86 131.41 129.69 127.16 123.15
8 130.16 133.93 136.77 139.68 141.17 141.50 140.90 141.01 149.16 161.02 155.89 153.80 150.81 145.92
9 143.92 149.26 154.19 158.65 161.48 162.83 162.72 163.19 172.72 186.57 180.97 178.66 175.21 169.51
10 156.66 163.83 170.39 176.21 179.90 182.13 183.08 184.46 195.62 211.90 206.37 203.82 199.98 193.52

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 52.29 51.24 50.67 50.40 49.98 49.46 48.85 49.35 52.36 56.60 55.19 54.71 54.03 52.96
5 67.06 66.29 65.96 65.88 65.48 64.85 64.03 64.35 68.16 73.60 71.45 70.69 69.62 68.03
6 82.01 81.71 81.64 81.94 81.72 81.11 80.17 80.32 84.97 91.69 88.77 87.69 86.13 83.71
7 96.33 96.86 97.61 98.42 98.41 97.94 96.99 97.02 102.59 110.69 107.02 105.61 103.54 100.23
8 110.09 111.69 113.32 114.87 115.42 115.20 114.29 114.25 120.79 130.31 126.02 124.28 121.71 117.39
9 123.15 126.05 128.79 130.88 132.01 132.22 131.57 131.72 139.29 150.26 145.44 143.43 140.38 135.22
10 135.44 139.37 143.36 146.77 148.74 149.45 149.09 149.46 158.10 170.61 165.37 163.09 159.55 153.57

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 206.374165.373
SC2 0 8 141.014114.245
SC3 -18 7 120.39898.528
SC4 -25 6 99.11581.643
SC5 -34 6 98.07782.043

Dimensions

Dimension drawing of EA-391AG10-C04 C
Dimension drawing
Dimensions as drawn
A 5238 mm
C 1587 mm
F 1032 mm
G 1150 mm
E1 2435 mm
E2 2400 mm
E 4835 mm
H 1334 mm
I 1750 mm
D IN 2 x Ø54
D OUT 2 x Ø80
Overall [mm]
Length 5238 mm
Width 1334 mm
Height 1750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.