EA-145AE10-C01 C
6.96 kW
Defrost: None
Product code: EA-430AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,569 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 20.4 m² |
| Inner volume | 9.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 60 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.4 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-430AC10-C01 C | None |
|---|---|
| EA-430AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.91 | 2.86 | 2.82 | 2.80 | 2.77 | 2.73 | 2.68 | 2.70 | 2.86 | 3.07 | 2.98 | 2.95 | 2.90 | 2.83 |
| 5 | 3.81 | 3.79 | 3.78 | 3.78 | 3.76 | 3.72 | 3.67 | 3.68 | 3.89 | 4.19 | 4.06 | 4.02 | 3.95 | 3.86 |
| 6 | 4.70 | 4.72 | 4.76 | 4.80 | 4.80 | 4.78 | 4.73 | 4.74 | 5.01 | 5.41 | 5.23 | 5.17 | 5.08 | 4.94 |
| 7 | 5.58 | 5.67 | 5.76 | 5.84 | 5.88 | 5.88 | 5.84 | 5.86 | 6.20 | 6.70 | 6.48 | 6.40 | 6.28 | 6.08 |
| 8 | 6.39 | 6.56 | 6.73 | 6.88 | 6.97 | 7.00 | 6.98 | 7.01 | 7.43 | 8.03 | 7.79 | 7.69 | 7.55 | 7.31 |
| 9 | 7.13 | 7.38 | 7.62 | 7.85 | 8.00 | 8.10 | 8.14 | 8.19 | 8.67 | 9.38 | 9.13 | 9.02 | 8.85 | 8.58 |
| 10 | 7.80 | 8.14 | 8.46 | 8.74 | 8.93 | 9.06 | 9.14 | 9.25 | 9.82 | 10.66 | 10.44 | 10.33 | 10.18 | 9.88 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.437 |
| SC2 | 0 | 8 | 7.013 |
| SC3 | -18 | 7 | 5.859 |
| SC4 | -25 | 6 | 4.761 |
| SC5 | -34 | 6 | 4.708 |
| A | 2107 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 455 mm |
| E2 | 438 mm |
| E | 1785 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.