EA-240AC7-C01 C
8.70 kW
Defrost: None
Product code: EA-430AC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 5,340 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 27.8 m² |
| Inner volume | 9.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 60 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.1 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-430AC7-C01 C | None |
|---|---|
| EA-430AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.62 | 3.59 | 3.58 | 3.58 | 3.56 | 3.52 | 3.47 | 3.51 | 3.72 | 4.02 | 3.91 | 3.87 | 3.81 | 3.72 |
| 5 | 4.66 | 4.70 | 4.74 | 4.78 | 4.77 | 4.74 | 4.69 | 4.72 | 5.00 | 5.40 | 5.24 | 5.18 | 5.11 | 5.00 |
| 6 | 5.70 | 5.82 | 5.92 | 6.01 | 6.05 | 6.04 | 5.99 | 6.03 | 6.38 | 6.89 | 6.68 | 6.59 | 6.48 | 6.29 |
| 7 | 6.66 | 6.87 | 7.08 | 7.25 | 7.35 | 7.38 | 7.35 | 7.39 | 7.83 | 8.47 | 8.21 | 8.10 | 7.95 | 7.71 |
| 8 | 7.49 | 7.80 | 8.08 | 8.35 | 8.52 | 8.60 | 8.64 | 8.73 | 9.27 | 10.06 | 9.78 | 9.66 | 9.48 | 9.19 |
| 9 | 8.26 | 8.68 | 9.02 | 9.37 | 9.60 | 9.75 | 9.83 | 9.94 | 10.56 | 11.46 | 11.20 | 11.08 | 10.91 | 10.63 |
| 10 | 8.97 | 9.47 | 9.96 | 10.39 | 10.70 | 10.90 | 11.01 | 11.16 | 11.85 | 12.87 | 12.59 | 12.46 | 12.27 | 11.94 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.588 |
| SC2 | 0 | 8 | 8.733 |
| SC3 | -18 | 7 | 7.300 |
| SC4 | -25 | 6 | 5.922 |
| SC5 | -34 | 6 | 5.734 |
| A | 2107 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 455 mm |
| E2 | 438 mm |
| E | 1785 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.