EA-330AE7-C01 C
7.66 kW
Defrost: None
Product code: EA-430AC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 5,433 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 24.7 m² |
| Inner volume | 9.4 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 61 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.2 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-430AC8-C01 C | None |
|---|---|
| EA-430AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.18 | 3.13 | 3.10 | 3.08 | 3.05 | 3.01 | 2.97 | 3.00 | 3.18 | 3.42 | 3.33 | 3.29 | 3.24 | 3.16 |
| 5 | 4.14 | 4.13 | 4.14 | 4.15 | 4.13 | 4.09 | 4.03 | 4.06 | 4.30 | 4.64 | 4.50 | 4.45 | 4.38 | 4.28 |
| 6 | 5.08 | 5.13 | 5.20 | 5.25 | 5.27 | 5.24 | 5.19 | 5.21 | 5.52 | 5.95 | 5.76 | 5.69 | 5.59 | 5.44 |
| 7 | 6.01 | 6.14 | 6.27 | 6.39 | 6.43 | 6.44 | 6.40 | 6.43 | 6.80 | 7.35 | 7.11 | 7.02 | 6.89 | 6.68 |
| 8 | 6.85 | 7.07 | 7.28 | 7.48 | 7.61 | 7.66 | 7.64 | 7.68 | 8.13 | 8.80 | 8.53 | 8.43 | 8.27 | 8.00 |
| 9 | 7.59 | 7.90 | 8.20 | 8.46 | 8.62 | 8.73 | 8.79 | 8.88 | 9.43 | 10.23 | 9.98 | 9.86 | 9.68 | 9.38 |
| 10 | 8.28 | 8.70 | 9.04 | 9.38 | 9.62 | 9.78 | 9.86 | 9.98 | 10.60 | 11.50 | 11.25 | 11.14 | 10.97 | 10.69 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.254 |
| SC2 | 0 | 8 | 7.678 |
| SC3 | -18 | 7 | 6.413 |
| SC4 | -25 | 6 | 5.195 |
| SC5 | -34 | 6 | 5.096 |
| A | 2107 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 455 mm |
| E2 | 438 mm |
| E | 1785 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.