EA-163FD10-C08 C
14.39 kW
Defrost: None
Product code: EA-435AC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 9,617 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 43.8 m² |
| Inner volume | 12.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 85 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-435AC6-C01 C | None |
|---|---|
| EA-435AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.82 | 5.93 | 6.03 | 6.11 | 6.12 | 6.08 | 6.01 | 6.10 | 6.48 | 7.00 | 6.80 | 6.72 | 6.61 | 6.44 |
| 5 | 7.40 | 7.68 | 7.93 | 8.14 | 8.23 | 8.23 | 8.18 | 8.30 | 8.81 | 9.53 | 9.25 | 9.15 | 9.02 | 8.82 |
| 6 | 8.74 | 9.19 | 9.59 | 9.95 | 10.13 | 10.27 | 10.32 | 10.49 | 11.16 | 12.13 | 11.83 | 11.70 | 11.51 | 11.21 |
| 7 | 9.91 | 10.55 | 11.05 | 11.55 | 11.90 | 12.12 | 12.23 | 12.43 | 13.22 | 14.37 | 14.06 | 13.93 | 13.74 | 13.41 |
| 8 | 10.98 | 11.73 | 12.49 | 13.17 | 13.65 | 13.97 | 14.14 | 14.38 | 15.30 | 16.65 | 16.29 | 16.14 | 15.91 | 15.52 |
| 9 | ≈ 11.87 | 12.90 | 13.86 | 14.72 | 15.35 | 15.79 | 16.05 | 16.34 | 17.39 | 18.93 | 18.56 | 18.38 | 18.12 | 17.66 |
| 10 | ≈ 12.73 | 13.97 | 15.15 | 16.21 | 17.00 | 17.57 | 17.93 | 18.30 | 19.49 | 21.23 | 20.84 | 20.65 | 20.35 | 19.83 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.838 |
| SC2 | 0 | 8 | 14.383 |
| SC3 | -18 | 7 | 11.711 |
| SC4 | -25 | 6 | 9.590 |
| SC5 | -34 | 6 | 8.845 |
| A | 2357 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 5175 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2357 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.