EA-163GD10-C13 C
18.42 kW
Defrost: None
Product code: EA-435AE4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 7,882 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 91.3 m² |
| Inner volume | 19.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 106 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-435AE4-C01 C | None |
|---|---|
| EA-435AE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.86 | 7.97 | 8.07 | 8.16 | 8.18 | 8.13 | 8.02 | 8.23 | 8.76 | 9.50 | 9.29 | 9.22 | 9.13 | 9.01 |
| 5 | 9.92 | 10.20 | 10.42 | 10.63 | 10.71 | 10.69 | 10.57 | 10.75 | 11.42 | 12.36 | 11.99 | 11.86 | 11.67 | 11.40 |
| 6 | 11.80 | 12.31 | 12.76 | 13.14 | 13.34 | 13.38 | 13.25 | 13.42 | 14.22 | 15.39 | 14.87 | 14.67 | 14.37 | 13.89 |
| 7 | 13.43 | 14.14 | 14.78 | 15.34 | 15.62 | 15.80 | 15.80 | 16.02 | 17.00 | 18.44 | 17.87 | 17.62 | 17.23 | 16.59 |
| 8 | 14.91 | 15.87 | 16.63 | 17.38 | 17.87 | 18.13 | 18.19 | 18.43 | 19.55 | 21.19 | 20.58 | 20.31 | 19.90 | 19.20 |
| 9 | 16.25 | 17.36 | 18.46 | 19.43 | 20.07 | 20.46 | 20.58 | 20.86 | 22.13 | 23.97 | 23.30 | 22.99 | 22.51 | 21.67 |
| 10 | ≈ 17.22 | 18.84 | 20.21 | 21.41 | 22.24 | 22.76 | 22.97 | 23.31 | 24.73 | 26.78 | 26.06 | 25.70 | 25.15 | 24.19 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 26.059 |
| SC2 | 0 | 8 | 18.429 |
| SC3 | -18 | 7 | 15.429 |
| SC4 | -25 | 6 | 12.760 |
| SC5 | -34 | 6 | 11.927 |
| A | 2357 mm |
|---|---|
| B | 573 mm |
| C | 525 mm |
| F | 395 mm |
| E1 | 5175 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2357 mm |
|---|---|
| Width | 573 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.