EA-263EC4-C06 C
23.79 kW
Defrost: None
Product code: EA-440AE4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 10,365 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 117.2 m² |
| Inner volume | 24.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 132 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-440AE4-C01 C | None |
|---|---|
| EA-440AE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.29 | 10.23 | 10.21 | 10.22 | 10.16 | 10.07 | 9.93 | 10.19 | 10.85 | 11.77 | 11.52 | 11.45 | 11.36 | 11.22 |
| 5 | 13.17 | 13.24 | 13.34 | 13.43 | 13.40 | 13.28 | 13.09 | 13.30 | 14.12 | 15.28 | 14.83 | 14.68 | 14.48 | 14.20 |
| 6 | 16.04 | 16.32 | 16.57 | 16.76 | 16.81 | 16.71 | 16.49 | 16.65 | 17.63 | 19.05 | 18.39 | 18.15 | 17.80 | 17.26 |
| 7 | 18.71 | 19.25 | 19.75 | 20.16 | 20.33 | 20.29 | 20.05 | 20.17 | 21.33 | 23.05 | 22.21 | 21.88 | 21.39 | 20.61 |
| 8 | 21.02 | 21.82 | 22.55 | 23.18 | 23.55 | 23.62 | 23.56 | 23.78 | 25.16 | 27.15 | 26.19 | 25.78 | 25.17 | 24.17 |
| 9 | 23.18 | 24.28 | 25.16 | 26.02 | 26.52 | 26.76 | 26.75 | 26.99 | 28.59 | 30.92 | 30.01 | 29.60 | 28.97 | 27.85 |
| 10 | 25.18 | 26.49 | 27.76 | 28.87 | 29.55 | 29.90 | 29.95 | 30.23 | 32.02 | 34.62 | 33.61 | 33.14 | 32.42 | 31.20 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 33.610 |
| SC2 | 0 | 8 | 23.782 |
| SC3 | -18 | 7 | 20.255 |
| SC4 | -25 | 6 | 16.571 |
| SC5 | -34 | 6 | 16.122 |
| A | 2567 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2235 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2567 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.