EA-263GC10-C08 C
29.47 kW
Defrost: None
Product code: EA-445AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 20,131 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 73.3 m² |
| Inner volume | 34.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 166 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø54 |
| EA-445AE10-C01 C | None |
|---|---|
| EA-445AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.96 | 11.99 | 12.02 | 12.05 | 11.97 | 11.82 | 11.61 | 11.74 | 12.45 | 13.39 | 12.95 | 12.78 | 12.54 | 12.18 |
| 5 | 15.32 | 15.65 | 15.93 | 16.16 | 16.22 | 16.15 | 15.95 | 16.09 | 17.05 | 18.39 | 17.79 | 17.58 | 17.29 | 16.88 |
| 6 | 18.61 | 19.26 | 19.85 | 20.35 | 20.61 | 20.64 | 20.52 | 20.69 | 21.92 | 23.68 | 22.92 | 22.63 | 22.20 | 21.53 |
| 7 | 21.44 | 22.42 | 23.33 | 24.14 | 24.68 | 24.92 | 25.04 | 25.38 | 26.92 | 29.14 | 28.28 | 27.94 | 27.41 | 26.55 |
| 8 | 23.94 | 25.30 | 26.40 | 27.52 | 28.30 | 28.78 | 29.02 | 29.42 | 31.26 | 33.97 | 33.18 | 32.84 | 32.33 | 31.46 |
| 9 | 26.24 | 27.85 | 29.47 | 30.91 | 31.94 | 32.61 | 32.99 | 33.49 | 35.60 | 38.68 | 37.84 | 37.45 | 36.86 | 35.84 |
| 10 | 28.33 | 30.37 | 32.38 | 34.17 | 35.49 | 36.40 | 36.93 | 37.56 | 39.94 | 43.43 | 42.53 | 42.10 | 41.44 | 40.28 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 42.527 |
| SC2 | 0 | 8 | 29.423 |
| SC3 | -18 | 7 | 24.385 |
| SC4 | -25 | 6 | 19.852 |
| SC5 | -34 | 6 | 18.772 |
| A | 3167 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2835 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø54 |
| Length | 3167 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.