EA-263FD10-C08 C
29.07 kW
Defrost: None
Product code: EA-450AC10-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 28,968 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 63.3 m² |
| Inner volume | 30.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 175 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 2,840 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 84.8 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-450AC10-C09 C | None |
|---|---|
| EA-450AC10-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.59 | 11.38 | 11.23 | 11.10 | 10.91 | 10.69 | 10.46 | 10.40 | 10.94 | 11.73 | 11.29 | 11.12 | 10.90 | 10.56 |
| 5 | 15.29 | 15.30 | 15.33 | 15.34 | 15.23 | 15.03 | 14.77 | 14.72 | 15.55 | 16.69 | 16.09 | 15.87 | 15.57 | 15.07 |
| 6 | 18.96 | 19.26 | 19.53 | 19.73 | 19.79 | 19.70 | 19.49 | 19.47 | 20.58 | 22.14 | 21.36 | 21.07 | 20.66 | 20.04 |
| 7 | 22.25 | 22.88 | 23.49 | 24.07 | 24.44 | 24.52 | 24.41 | 24.46 | 25.89 | 27.93 | 27.05 | 26.71 | 26.18 | 25.38 |
| 8 | 25.11 | 26.07 | 26.97 | 27.71 | 28.27 | 28.63 | 28.81 | 29.09 | 30.89 | 33.53 | 32.78 | 32.48 | 31.98 | 31.07 |
| 9 | 27.77 | 29.12 | 30.22 | 31.34 | 32.13 | 32.65 | 32.96 | 33.31 | 35.39 | 38.45 | 37.64 | 37.31 | 36.81 | 35.98 |
| 10 | 30.25 | 31.86 | 33.46 | 34.90 | 35.94 | 36.66 | 37.11 | 37.57 | 39.93 | 43.40 | 42.56 | 42.19 | 41.64 | 40.71 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 42.561 |
| SC2 | 0 | 8 | 29.089 |
| SC3 | -18 | 7 | 24.243 |
| SC4 | -25 | 6 | 19.532 |
| SC5 | -34 | 6 | 19.048 |
| A | 3787 mm |
|---|---|
| B | 590 mm |
| C | 715 mm |
| F | 510 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 3435 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 3787 mm |
|---|---|
| Width | 590 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.