EA-263GD4-C08 C
48.10 kW
Defrost: None
Product code: EA-450AG8-C10 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 24,660 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 153.3 m² |
| Inner volume | 57.8 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 265 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 2,760 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø54 |
| EA-450AG8-C10 C | None |
|---|---|
| EA-450AG8-C10 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 19.52 | 20.09 | 20.57 | 20.95 | 21.08 | 21.00 | 20.76 | 21.17 | 22.50 | 24.34 | 23.69 | 23.48 | 23.18 | 22.72 |
| 5 | 24.49 | 25.62 | 26.61 | 27.44 | 27.82 | 27.96 | 27.82 | 28.23 | 29.97 | 32.45 | 31.46 | 31.10 | 30.58 | 29.79 |
| 6 | 28.80 | 30.50 | 32.05 | 33.40 | 34.29 | 34.66 | 34.86 | 35.45 | 37.66 | 40.81 | 39.64 | 39.17 | 38.46 | 37.30 |
| 7 | 32.48 | 34.83 | 36.71 | 38.58 | 39.89 | 40.71 | 41.10 | 41.79 | 44.43 | 48.32 | 47.17 | 46.69 | 45.94 | 44.66 |
| 8 | ≈ 35.82 | 38.54 | 41.29 | 43.74 | 45.52 | 46.66 | 47.29 | 48.15 | 51.20 | 55.68 | 54.44 | 53.87 | 52.99 | 51.46 |
| 9 | ≈ 38.80 | 42.18 | 45.60 | 48.68 | 50.94 | 52.52 | 53.44 | 54.50 | 57.99 | 63.08 | 61.77 | 61.13 | 60.13 | 58.35 |
| 10 | 39.60 | 45.51 | 49.64 | 53.36 | 56.23 | 58.26 | 59.51 | 60.83 | 64.76 | 70.48 | 69.14 | 68.44 | 67.33 | 65.32 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 16.96 | 17.24 | 17.50 | 17.71 | 17.75 | 17.64 | 17.41 | 17.80 | 18.95 | 20.51 | 19.99 | 19.82 | 19.58 | 19.26 |
| 5 | 21.22 | 21.92 | 22.55 | 23.07 | 23.31 | 23.31 | 23.10 | 23.45 | 24.89 | 26.94 | 26.09 | 25.79 | 25.35 | 24.68 |
| 6 | 25.37 | 26.54 | 27.59 | 28.47 | 28.97 | 29.09 | 28.97 | 29.32 | 31.09 | 33.67 | 32.58 | 32.15 | 31.50 | 30.46 |
| 7 | 28.98 | 30.62 | 32.12 | 33.44 | 34.29 | 34.65 | 34.79 | 35.26 | 37.40 | 40.50 | 39.26 | 38.74 | 37.94 | 36.58 |
| 8 | 32.14 | 34.33 | 36.33 | 37.84 | 39.04 | 39.72 | 40.01 | 40.62 | 43.13 | 46.81 | 45.63 | 45.09 | 44.26 | 42.85 |
| 9 | 35.02 | 37.78 | 40.03 | 42.26 | 43.79 | 44.78 | 45.24 | 45.97 | 48.82 | 52.98 | 51.71 | 51.10 | 50.16 | 48.56 |
| 10 | 37.61 | 40.69 | 43.77 | 46.46 | 48.45 | 49.76 | 50.43 | 51.32 | 54.53 | 59.18 | 57.83 | 57.16 | 56.11 | 54.33 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 69.138 | 57.830 |
| SC2 | 0 | 8 | 48.149 | 40.620 |
| SC3 | -18 | 7 | 39.164 | 33.830 |
| SC4 | -25 | 6 | 32.053 | 27.588 |
| SC5 | -34 | 6 | 29.196 | 25.651 |
| A | 3787 mm |
|---|---|
| B | 740 mm |
| C | 715 mm |
| F | 660 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 3435 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø54 |
| Length | 3787 mm |
|---|---|
| Width | 690 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.