EA-563ED4-C06 C
69.55 kW
Defrost: None
Product code: EA-480GC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 88,327 m³/h |
|---|---|
| Air throw | 49 m |
| External surface | 253.9 m² |
| Inner volume | 107.1 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 676 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-480GC10-C01 C | None |
|---|---|
| EA-480GC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 28.71 | 28.39 | 28.16 | 27.98 | 27.66 | 27.25 | 26.81 | 26.74 | 28.20 | 30.31 | 29.32 | 28.95 | 28.44 | 27.66 |
| 5 | 37.33 | 37.48 | 37.61 | 37.72 | 37.48 | 37.09 | 36.57 | 36.50 | 38.57 | 41.49 | 40.13 | 39.63 | 38.92 | 37.78 |
| 6 | 45.46 | 46.36 | 47.13 | 47.74 | 47.87 | 47.65 | 47.18 | 47.03 | 49.72 | 53.53 | 51.78 | 51.13 | 50.19 | 48.74 |
| 7 | 53.06 | 54.61 | 56.18 | 57.49 | 58.14 | 58.30 | 58.06 | 58.12 | 61.50 | 66.32 | 64.24 | 63.44 | 62.24 | 60.36 |
| 8 | 59.41 | 61.99 | 64.35 | 66.44 | 67.79 | 68.60 | 68.97 | 69.45 | 73.56 | 79.51 | 77.20 | 76.29 | 74.92 | 72.71 |
| 9 | 65.32 | 68.85 | 72.04 | 74.83 | 76.73 | 77.91 | 78.55 | 79.27 | 84.17 | 91.33 | 89.28 | 88.44 | 87.19 | 85.10 |
| 10 | 70.77 | 75.31 | 79.42 | 83.03 | 85.55 | 87.18 | 88.14 | 89.08 | 94.62 | 102.74 | 100.54 | 99.61 | 98.21 | 95.86 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 24.96 | 24.55 | 24.29 | 24.13 | 23.87 | 23.57 | 23.24 | 23.34 | 24.64 | 26.54 | 25.77 | 25.48 | 25.07 | 24.46 |
| 5 | 32.44 | 32.18 | 32.15 | 32.16 | 31.96 | 31.63 | 31.21 | 31.25 | 33.07 | 35.63 | 34.55 | 34.16 | 33.61 | 32.78 |
| 6 | 39.64 | 39.97 | 40.29 | 40.60 | 40.57 | 40.27 | 39.84 | 39.85 | 42.15 | 45.41 | 43.96 | 43.43 | 42.67 | 41.50 |
| 7 | 46.53 | 47.49 | 48.36 | 49.10 | 49.36 | 49.27 | 48.83 | 48.86 | 51.66 | 55.72 | 53.95 | 53.28 | 52.29 | 50.74 |
| 8 | 52.99 | 54.48 | 56.00 | 57.31 | 58.01 | 58.22 | 58.06 | 58.17 | 61.56 | 66.47 | 64.44 | 63.63 | 62.44 | 60.53 |
| 9 | 58.51 | 60.90 | 63.08 | 65.06 | 66.33 | 67.10 | 67.36 | 67.63 | 71.63 | 77.46 | 75.22 | 74.31 | 72.96 | 70.73 |
| 10 | 63.68 | 66.86 | 69.75 | 72.31 | 74.03 | 75.10 | 75.65 | 76.29 | 80.98 | 87.84 | 85.83 | 84.98 | 83.65 | 81.15 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 100.536 | 85.830 |
| SC2 | 0 | 8 | 69.446 | 58.165 |
| SC3 | -18 | 7 | 57.814 | 49.253 |
| SC4 | -25 | 6 | 47.127 | 40.293 |
| SC5 | -34 | 6 | 45.726 | 39.770 |
| A | 5615 mm |
|---|---|
| B | 950 mm |
| C | 1430 mm |
| F | 910 mm |
| G | 1015 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 5235 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 5615 mm |
|---|---|
| Width | 950 mm |
| Height | 1430 mm |
Our engineers answer with a selection for your conditions.