EA-163EE4-C06 C
15.58 kW
Defrost: None
Product code: EA-535AC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 12,490 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 42.4 m² |
| Inner volume | 16.1 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 103 kg |
| Quantity | 5 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 825 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-535AC8-C01 C | None |
|---|---|
| EA-535AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.31 | 6.28 | 6.27 | 6.26 | 6.20 | 6.12 | 6.01 | 6.05 | 6.39 | 6.87 | 6.65 | 6.57 | 6.45 | 6.27 |
| 5 | 8.17 | 8.29 | 8.39 | 8.48 | 8.48 | 8.42 | 8.31 | 8.36 | 8.85 | 9.53 | 9.23 | 9.12 | 8.97 | 8.75 |
| 6 | 10.00 | 10.29 | 10.55 | 10.77 | 10.87 | 10.86 | 10.79 | 10.85 | 11.49 | 12.40 | 12.00 | 11.85 | 11.64 | 11.31 |
| 7 | 11.57 | 12.03 | 12.46 | 12.84 | 13.10 | 13.21 | 13.28 | 13.42 | 14.22 | 15.38 | 14.93 | 14.76 | 14.50 | 14.07 |
| 8 | 12.96 | 13.62 | 14.16 | 14.70 | 15.07 | 15.30 | 15.42 | 15.61 | 16.59 | 18.02 | 17.63 | 17.46 | 17.20 | 16.77 |
| 9 | 14.26 | 15.05 | 15.84 | 16.55 | 17.06 | 17.39 | 17.58 | 17.82 | 18.94 | 20.58 | 20.14 | 19.95 | 19.65 | 19.15 |
| 10 | 15.44 | 16.45 | 17.46 | 18.36 | 19.00 | 19.45 | 19.73 | 20.03 | 21.30 | 23.16 | 22.69 | 22.47 | 22.14 | 21.56 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 22.686 |
| SC2 | 0 | 8 | 15.614 |
| SC3 | -18 | 7 | 12.959 |
| SC4 | -25 | 6 | 10.546 |
| SC5 | -34 | 6 | 10.073 |
| A | 2857 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2535 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2857 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.