EA-263ED7-C06 C
22.00 kW
Defrost: None
Product code: EA-540AC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,153 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 61.0 m² |
| Inner volume | 19.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 125 kg |
| Quantity | 5 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-540AC7-C01 C | None |
|---|---|
| EA-540AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.82 | 9.00 | 9.14 | 9.25 | 9.25 | 9.19 | 9.07 | 9.15 | 9.70 | 10.45 | 10.12 | 9.99 | 9.81 | 9.54 |
| 5 | 11.25 | 11.69 | 12.07 | 12.39 | 12.54 | 12.55 | 12.47 | 12.59 | 13.35 | 14.42 | 13.98 | 13.82 | 13.60 | 13.27 |
| 6 | 13.28 | 13.96 | 14.59 | 15.13 | 15.42 | 15.65 | 15.76 | 15.98 | 16.99 | 18.46 | 18.05 | 17.88 | 17.59 | 17.13 |
| 7 | 15.06 | 15.90 | 16.81 | 17.59 | 18.14 | 18.50 | 18.70 | 18.98 | 20.18 | 21.94 | 21.49 | 21.30 | 21.02 | 20.55 |
| 8 | 16.68 | 17.84 | 19.01 | 20.05 | 20.81 | 21.33 | 21.64 | 22.00 | 23.41 | 25.48 | 24.97 | 24.76 | 24.43 | 23.86 |
| 9 | ≈ 18.03 | 19.61 | 21.09 | 22.42 | 23.42 | 24.13 | 24.58 | 25.03 | 26.65 | 29.02 | 28.50 | 28.26 | 27.89 | 27.20 |
| 10 | ≈ 19.33 | 21.23 | 23.05 | 24.69 | 25.94 | 26.86 | 27.47 | 28.05 | 29.89 | 32.58 | 32.05 | 31.79 | 31.37 | 30.59 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 32.048 |
| SC2 | 0 | 8 | 22.002 |
| SC3 | -18 | 7 | 17.838 |
| SC4 | -25 | 6 | 14.586 |
| SC5 | -34 | 6 | 13.439 |
| A | 3117 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2785 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 3117 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.