EA-363ED7-C11 C
46.33 kW
Defrost: None
Product code: EA-550AE8-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 31,647 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 135.6 m² |
| Inner volume | 52.1 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 252 kg |
| Quantity | 5 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 3,550 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø54 |
| EA-550AE8-C09 C | None |
|---|---|
| EA-550AE8-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 18.80 | 18.72 | 18.67 | 18.62 | 18.43 | 18.15 | 17.80 | 18.02 | 19.05 | 20.47 | 19.80 | 19.55 | 19.20 | 18.66 |
| 5 | 24.34 | 24.70 | 25.00 | 25.24 | 25.21 | 24.99 | 24.61 | 24.80 | 26.27 | 28.31 | 27.38 | 27.07 | 26.63 | 25.98 |
| 6 | 29.78 | 30.66 | 31.44 | 32.07 | 32.33 | 32.23 | 31.93 | 32.14 | 34.03 | 36.70 | 35.44 | 34.98 | 34.32 | 33.30 |
| 7 | 34.46 | 35.86 | 37.16 | 38.30 | 39.02 | 39.40 | 39.40 | 39.73 | 42.07 | 45.49 | 44.04 | 43.48 | 42.63 | 41.28 |
| 8 | 38.60 | 40.60 | 42.20 | 43.81 | 44.88 | 45.52 | 45.78 | 46.33 | 49.20 | 53.41 | 52.10 | 51.57 | 50.75 | 49.41 |
| 9 | 42.42 | 44.83 | 47.22 | 49.33 | 50.80 | 51.72 | 52.18 | 52.85 | 56.14 | 60.95 | 59.53 | 58.91 | 57.98 | 56.40 |
| 10 | 45.92 | 48.98 | 52.01 | 54.70 | 56.58 | 57.84 | 58.53 | 59.40 | 63.12 | 68.56 | 67.05 | 66.36 | 65.31 | 63.47 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 67.050 |
| SC2 | 0 | 8 | 46.329 |
| SC3 | -18 | 7 | 38.634 |
| SC4 | -25 | 6 | 31.437 |
| SC5 | -34 | 6 | 30.012 |
| A | 4387 mm |
|---|---|
| B | 640 mm |
| C | 715 mm |
| F | 560 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø54 |
| Length | 4387 mm |
|---|---|
| Width | 640 mm |
| Height | 715 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.