EA-363EE10-C11 C
49.05 kW
Defrost: None
Product code: EA-563EC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 43,812 m³/h |
|---|---|
| Air throw | 26 m |
| External surface | 225.3 m² |
| Inner volume | 70.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 383 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 3,000 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 81.4 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-563EC7-C01 C | None |
|---|---|
| EA-563EC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 21.20 | 20.77 | 20.52 | 20.39 | 20.21 | 20.01 | 19.79 | 19.96 | 21.11 | 22.79 | 22.21 | 22.00 | 21.70 | 21.26 |
| 5 | 27.62 | 27.32 | 27.12 | 27.07 | 26.89 | 26.62 | 26.30 | 26.42 | 27.99 | 30.21 | 29.39 | 29.10 | 28.69 | 28.09 |
| 6 | 33.95 | 33.97 | 34.07 | 34.19 | 34.09 | 33.80 | 33.43 | 33.49 | 35.45 | 38.23 | 37.08 | 36.67 | 36.09 | 35.21 |
| 7 | 40.08 | 40.58 | 41.06 | 41.49 | 41.57 | 41.32 | 40.96 | 41.01 | 43.37 | 46.78 | 45.33 | 44.78 | 44.00 | 42.79 |
| 8 | 45.91 | 46.81 | 47.80 | 48.66 | 49.04 | 49.06 | 48.79 | 48.85 | 51.69 | 55.79 | 54.06 | 53.39 | 52.40 | 50.84 |
| 9 | 50.78 | 52.38 | 53.89 | 55.27 | 56.13 | 56.60 | 56.75 | 56.91 | 60.25 | 65.11 | 63.15 | 62.37 | 61.22 | 59.36 |
| 10 | 55.47 | 57.70 | 59.74 | 61.58 | 62.75 | 63.44 | 63.72 | 64.18 | 68.09 | 73.81 | 72.05 | 71.31 | 70.23 | 68.12 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 72.045 |
| SC2 | 0 | 8 | 48.853 |
| SC3 | -18 | 7 | 41.560 |
| SC4 | -25 | 6 | 34.070 |
| SC5 | -34 | 6 | 34.004 |
| A | 4415 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 4415 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.