EA-463FC7-C08 C
56.96 kW
Defrost: None
Product code: EA-563ED7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 41,746 m³/h |
|---|---|
| Air throw | 25 m |
| External surface | 281.7 m² |
| Inner volume | 84.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 442 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 3,000 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 81.1 dB(A) |
| Energy class | C |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-563ED7-C01 C | None |
|---|---|
| EA-563ED7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 25.23 | 24.72 | 24.43 | 24.29 | 24.09 | 23.86 | 23.61 | 23.89 | 25.32 | 27.36 | 26.70 | 26.45 | 26.11 | 25.59 |
| 5 | 32.77 | 32.30 | 32.12 | 32.05 | 31.84 | 31.54 | 31.16 | 31.36 | 33.24 | 35.91 | 34.95 | 34.62 | 34.15 | 33.46 |
| 6 | 40.23 | 40.15 | 40.21 | 40.32 | 40.15 | 39.83 | 39.37 | 39.50 | 41.81 | 45.12 | 43.77 | 43.29 | 42.60 | 41.56 |
| 7 | 47.49 | 47.92 | 48.36 | 48.80 | 48.84 | 48.58 | 48.10 | 48.15 | 50.94 | 54.95 | 53.21 | 52.54 | 51.60 | 50.15 |
| 8 | 54.43 | 55.49 | 56.30 | 57.17 | 57.53 | 57.46 | 57.06 | 57.12 | 60.42 | 65.21 | 63.11 | 62.30 | 61.10 | 59.18 |
| 9 | 60.53 | 62.23 | 63.86 | 65.36 | 66.28 | 66.51 | 66.25 | 66.37 | 70.22 | 75.85 | 73.47 | 72.50 | 71.07 | 68.74 |
| 10 | 66.20 | 68.60 | 70.81 | 72.82 | 74.08 | 74.73 | 74.95 | 75.46 | 80.01 | 86.66 | 84.06 | 82.95 | 81.31 | 78.60 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 84.056 |
| SC2 | 0 | 8 | 57.122 |
| SC3 | -18 | 7 | 48.853 |
| SC4 | -25 | 6 | 40.207 |
| SC5 | -34 | 6 | 40.267 |
| A | 4415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 4415 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.