EA-463FG4-C13 C
124.63 kW
Defrost: None
Product code: EA-563FE4-C13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 81,093 m³/h |
|---|---|
| Air throw | 48 m |
| External surface | 626.5 m² |
| Inner volume | 127.0 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 677 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 13,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | E |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø80 |
| EA-563FE4-C13 C | None |
|---|---|
| EA-563FE4-C13 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 51.90 | 52.97 | 53.82 | 54.48 | 54.59 | 54.33 | 53.79 | 54.35 | 57.64 | 62.20 | 60.54 | 59.91 | 58.98 | 57.64 |
| 5 | 64.98 | 67.23 | 69.48 | 71.29 | 72.17 | 72.35 | 71.97 | 72.59 | 76.97 | 83.19 | 80.92 | 80.10 | 78.91 | 77.13 |
| 6 | 75.61 | 79.65 | 83.27 | 86.38 | 88.40 | 89.56 | 90.02 | 91.20 | 96.90 | 105.16 | 102.89 | 101.78 | 100.16 | 97.60 |
| 7 | 85.28 | 90.99 | 96.13 | 100.56 | 103.58 | 105.41 | 106.30 | 107.72 | 114.48 | 124.29 | 121.55 | 120.45 | 118.82 | 116.14 |
| 8 | ≈ 94.04 | 101.54 | 108.38 | 114.33 | 118.52 | 121.24 | 122.68 | 124.44 | 132.27 | 143.72 | 140.56 | 139.27 | 137.30 | 134.01 |
| 9 | ≈ 101.92 | 111.27 | 119.93 | 127.57 | 133.14 | 136.89 | 139.06 | 141.25 | 150.22 | 163.36 | 159.88 | 158.39 | 156.11 | 152.24 |
| 10 | ≈ 108.97 | 120.18 | 130.79 | 140.25 | 147.35 | 152.23 | 155.29 | 158.07 | 168.21 | 183.04 | 179.40 | 177.74 | 175.19 | 170.76 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 44.95 | 45.35 | 45.74 | 46.01 | 46.03 | 45.80 | 45.39 | 46.18 | 49.11 | 53.19 | 52.03 | 51.60 | 50.94 | 49.92 |
| 5 | 56.54 | 58.00 | 59.24 | 60.24 | 60.58 | 60.28 | 59.80 | 60.49 | 64.21 | 69.48 | 67.63 | 66.98 | 66.08 | 64.76 |
| 6 | 67.39 | 69.78 | 72.21 | 74.20 | 75.23 | 75.50 | 75.17 | 75.85 | 80.42 | 86.97 | 84.43 | 83.48 | 82.09 | 79.91 |
| 7 | 76.21 | 80.12 | 83.65 | 86.70 | 88.64 | 89.70 | 90.06 | 91.13 | 96.78 | 105.02 | 102.31 | 101.15 | 99.43 | 96.68 |
| 8 | 84.50 | 89.83 | 94.63 | 98.76 | 101.52 | 103.11 | 103.80 | 105.01 | 111.51 | 121.04 | 118.17 | 117.05 | 115.34 | 112.47 |
| 9 | 92.08 | 98.92 | 105.13 | 110.51 | 114.21 | 116.45 | 117.55 | 119.03 | 126.40 | 137.22 | 134.16 | 132.84 | 130.84 | 127.44 |
| 10 | ≈ 98.94 | 107.34 | 115.10 | 121.86 | 126.57 | 129.65 | 131.28 | 133.11 | 141.43 | 153.59 | 150.32 | 148.84 | 146.57 | 142.66 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 179.395 | 150.319 |
| SC2 | 0 | 8 | 124.435 | 105.014 |
| SC3 | -18 | 7 | 101.920 | 87.593 |
| SC4 | -25 | 6 | 83.265 | 72.207 |
| SC5 | -34 | 6 | 76.569 | 67.628 |
| A | 5415 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| G | 1110 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø80 |
| Length | 5415 mm |
|---|---|
| Width | 1110 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.