EA-563FD7-C13 C
86.24 kW
Defrost: None
Product code: EA-563FE7-C19 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 57,560 m³/h |
|---|---|
| Air throw | 34 m |
| External surface | 422.5 m² |
| Inner volume | 127.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 541 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,250 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FE7-C19 C | None |
|---|---|
| EA-563FE7-C19 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 36.64 | 36.41 | 36.32 | 36.33 | 36.15 | 35.86 | 35.51 | 35.67 | 37.79 | 40.78 | 39.70 | 39.30 | 38.73 | 37.86 |
| 5 | 46.97 | 47.27 | 47.60 | 47.92 | 47.83 | 47.58 | 47.16 | 47.27 | 50.04 | 54.01 | 52.49 | 51.94 | 51.16 | 49.97 |
| 6 | 56.75 | 57.91 | 58.95 | 59.84 | 60.16 | 60.07 | 59.69 | 59.66 | 63.16 | 68.18 | 66.20 | 65.45 | 64.38 | 62.71 |
| 7 | 65.93 | 67.84 | 69.79 | 71.47 | 72.36 | 72.67 | 72.51 | 72.70 | 76.98 | 83.17 | 80.76 | 79.82 | 78.43 | 76.24 |
| 8 | 73.72 | 76.87 | 79.76 | 82.34 | 84.02 | 85.05 | 85.54 | 86.04 | 91.17 | 98.63 | 95.90 | 94.81 | 93.19 | 90.54 |
| 9 | 80.98 | 85.25 | 89.13 | 92.55 | 94.87 | 96.32 | 97.11 | 97.98 | 104.02 | 112.87 | 110.36 | 109.32 | 107.75 | 105.15 |
| 10 | 87.66 | 93.15 | 98.15 | 102.52 | 105.54 | 107.51 | 108.66 | 109.79 | 116.60 | 126.57 | 123.86 | 122.70 | 120.94 | 117.98 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 32.52 | 32.17 | 32.02 | 32.01 | 31.87 | 31.64 | 31.37 | 31.62 | 33.54 | 36.28 | 35.43 | 35.12 | 34.65 | 33.93 |
| 5 | 41.65 | 41.61 | 41.63 | 41.83 | 41.78 | 41.55 | 41.19 | 41.37 | 43.83 | 47.36 | 46.09 | 45.63 | 44.99 | 44.02 |
| 6 | 50.44 | 50.99 | 51.56 | 52.11 | 52.24 | 52.05 | 51.69 | 51.81 | 54.86 | 59.25 | 57.54 | 56.91 | 55.99 | 54.57 |
| 7 | 58.84 | 60.16 | 61.38 | 62.45 | 62.77 | 62.84 | 62.57 | 62.71 | 66.38 | 71.70 | 69.60 | 68.79 | 67.59 | 65.69 |
| 8 | 66.73 | 68.69 | 70.70 | 72.45 | 73.43 | 73.82 | 73.74 | 73.95 | 78.30 | 84.66 | 82.21 | 81.24 | 79.78 | 77.42 |
| 9 | 73.48 | 76.54 | 79.35 | 81.89 | 83.54 | 84.52 | 84.98 | 85.38 | 90.45 | 97.85 | 95.16 | 94.04 | 92.36 | 89.57 |
| 10 | 79.85 | 83.89 | 87.57 | 90.83 | 92.98 | 94.35 | 95.05 | 95.90 | 101.77 | 110.36 | 107.86 | 106.78 | 105.14 | 101.96 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 123.859 | 107.861 |
| SC2 | 0 | 8 | 86.043 | 73.945 |
| SC3 | -18 | 7 | 71.903 | 62.705 |
| SC4 | -25 | 6 | 58.950 | 51.555 |
| SC5 | -34 | 6 | 57.083 | 50.627 |
| A | 5415 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.