EA-150AE8-C09 C
10.20 kW
Defrost: None
Product code: EA-630BC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,584 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 31.1 m² |
| Inner volume | 11.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 77 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 72.3 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-630BC8-C01 C | None |
|---|---|
| EA-630BC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.10 | 4.14 | 4.18 | 4.21 | 4.20 | 4.17 | 4.11 | 4.17 | 4.42 | 4.77 | 4.64 | 4.58 | 4.51 | 4.39 |
| 5 | 5.26 | 5.37 | 5.50 | 5.60 | 5.65 | 5.65 | 5.60 | 5.66 | 6.00 | 6.49 | 6.29 | 6.23 | 6.13 | 6.00 |
| 6 | 6.32 | 6.58 | 6.82 | 7.03 | 7.15 | 7.19 | 7.17 | 7.24 | 7.68 | 8.31 | 8.07 | 7.98 | 7.85 | 7.63 |
| 7 | 7.24 | 7.62 | 7.97 | 8.28 | 8.46 | 8.60 | 8.67 | 8.79 | 9.35 | 10.16 | 9.92 | 9.82 | 9.66 | 9.39 |
| 8 | 8.07 | 8.58 | 9.00 | 9.42 | 9.72 | 9.92 | 10.03 | 10.18 | 10.83 | 11.78 | 11.54 | 11.43 | 11.27 | 11.01 |
| 9 | 8.82 | 9.42 | 10.02 | 10.56 | 10.95 | 11.23 | 11.39 | 11.58 | 12.32 | 13.41 | 13.15 | 13.03 | 12.85 | 12.54 |
| 10 | 9.50 | 10.25 | 10.99 | 11.65 | 12.15 | 12.51 | 12.74 | 12.98 | 13.81 | 15.04 | 14.77 | 14.64 | 14.44 | 14.09 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.770 |
| SC2 | 0 | 8 | 10.182 |
| SC3 | -18 | 7 | 8.378 |
| SC4 | -25 | 6 | 6.823 |
| SC5 | -34 | 6 | 6.383 |
| A | 2557 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2557 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |