EA-163FD10-C19 C
13.05 kW
Defrost: None
Product code: EA-630BE6-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,449 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 59.9 m² |
| Inner volume | 16.5 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 72 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 720 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-630BE6-C05 C | None |
|---|---|
| EA-630BE6-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.59 | 5.65 | 5.72 | 5.79 | 5.80 | 5.77 | 5.71 | 5.83 | 6.21 | 6.73 | 6.57 | 6.51 | 6.45 | 6.36 |
| 5 | 6.98 | 7.16 | 7.34 | 7.48 | 7.55 | 7.54 | 7.48 | 7.58 | 8.05 | 8.72 | 8.45 | 8.35 | 8.21 | 7.99 |
| 6 | 8.34 | 8.66 | 8.95 | 9.20 | 9.32 | 9.36 | 9.31 | 9.41 | 9.97 | 10.80 | 10.45 | 10.31 | 10.10 | 9.76 |
| 7 | 9.55 | 10.02 | 10.45 | 10.82 | 11.06 | 11.19 | 11.17 | 11.25 | 11.93 | 12.91 | 12.51 | 12.34 | 12.08 | 11.63 |
| 8 | 10.61 | 11.24 | 11.82 | 12.26 | 12.60 | 12.78 | 12.84 | 13.01 | 13.80 | 14.96 | 14.56 | 14.38 | 14.10 | 13.56 |
| 9 | 11.59 | 12.40 | 13.06 | 13.70 | 14.14 | 14.40 | 14.51 | 14.71 | 15.61 | 16.91 | 16.48 | 16.27 | 15.94 | 15.37 |
| 10 | 12.48 | 13.39 | 14.30 | 15.10 | 15.65 | 16.01 | 16.17 | 16.41 | 17.42 | 18.87 | 18.40 | 18.17 | 17.80 | 17.16 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.402 |
| SC2 | 0 | 8 | 13.008 |
| SC3 | -18 | 7 | 10.932 |
| SC4 | -25 | 6 | 8.951 |
| SC5 | -34 | 6 | 8.419 |
| A | 2557 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2407 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.