EA-HL-250AC10-A10 C
19.16 kW
Defrost: None
Product code: EA-HL-150AG4-A10 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,731 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 101.4 m² |
| Inner volume | 21.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 132 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 690 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-HL-150AG4-A10 C | None |
|---|---|
| EA-HL-150AG4-A10 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.97 | 8.08 | 8.19 | 8.30 | 8.34 | 8.32 | 8.26 | 8.38 | 8.91 | 9.66 | 9.42 | 9.35 | 9.24 | 9.08 |
| 5 | 9.89 | 10.17 | 10.42 | 10.64 | 10.75 | 10.77 | 10.71 | 10.81 | 11.47 | 12.42 | 12.07 | 11.94 | 11.75 | 11.46 |
| 6 | 11.77 | 12.24 | 12.66 | 13.02 | 13.20 | 13.28 | 13.25 | 13.35 | 14.15 | 15.32 | 14.86 | 14.67 | 14.39 | 13.93 |
| 7 | 13.45 | 14.12 | 14.74 | 15.28 | 15.63 | 15.82 | 15.83 | 15.94 | 16.86 | 18.25 | 17.71 | 17.48 | 17.13 | 16.53 |
| 8 | 14.91 | 15.82 | 16.64 | 17.26 | 17.76 | 18.05 | 18.18 | 18.37 | 19.49 | 21.13 | 20.58 | 20.33 | 19.93 | 19.20 |
| 9 | 16.24 | 17.40 | 18.35 | 19.27 | 19.91 | 20.30 | 20.50 | 20.74 | 22.01 | 23.85 | 23.25 | 22.97 | 22.53 | 21.75 |
| 10 | ≈ 17.45 | 18.76 | 20.05 | 21.19 | 22.00 | 22.54 | 22.82 | 23.11 | 24.53 | 26.59 | 25.94 | 25.63 | 25.13 | 24.25 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.78 | 6.81 | 6.87 | 6.93 | 6.95 | 6.93 | 6.87 | 7.00 | 7.45 | 8.08 | 7.89 | 7.83 | 7.74 | 7.62 |
| 5 | 8.42 | 8.56 | 8.70 | 8.83 | 8.89 | 8.88 | 8.81 | 8.91 | 9.45 | 10.25 | 9.95 | 9.84 | 9.68 | 9.43 |
| 6 | 10.00 | 10.27 | 10.52 | 10.75 | 10.86 | 10.88 | 10.81 | 10.90 | 11.54 | 12.50 | 12.10 | 11.95 | 11.71 | 11.32 |
| 7 | 11.55 | 11.97 | 12.35 | 12.68 | 12.84 | 12.90 | 12.85 | 12.93 | 13.69 | 14.80 | 14.34 | 14.14 | 13.83 | 13.32 |
| 8 | 12.94 | 13.54 | 14.09 | 14.55 | 14.83 | 14.94 | 14.91 | 15.00 | 15.88 | 17.15 | 16.62 | 16.38 | 16.02 | 15.38 |
| 9 | 14.20 | 14.97 | 15.68 | 16.29 | 16.69 | 16.90 | 16.91 | 17.06 | 18.06 | 19.50 | 18.91 | 18.64 | 18.22 | 17.47 |
| 10 | 15.34 | 16.32 | 17.21 | 17.90 | 18.42 | 18.71 | 18.82 | 18.99 | 20.13 | 21.77 | 21.18 | 20.89 | 20.45 | 19.59 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 25.941 | 21.178 |
| SC2 | 0 | 8 | 18.370 | 15.000 |
| SC3 | -18 | 7 | 15.438 | 12.740 |
| SC4 | -25 | 6 | 12.659 | 10.519 |
| SC5 | -34 | 6 | 11.890 | 10.068 |
| A | 1387 mm |
|---|---|
| B | 740 mm |
| C | 875 mm |
| F | 660 mm |
| E | 1035 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1387 mm |
|---|---|
| Width | 740 mm |
| Height | 875 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.