EB-430AB4-B05 C
7.15 kW
Defrost: None
Product code: EB-145AE7-B07 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,832 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 18.1 m² |
| Inner volume | 5.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 46 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,360 rpm |
| Power | 480 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-145AE7-B07 C | None |
|---|---|
| EB-145AE7-B07 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.91 | 2.85 | 2.81 | 2.77 | 2.73 | 2.68 | 2.62 | 2.66 | 2.81 | 3.02 | 2.92 | 2.89 | 2.84 | 2.77 |
| 5 | 3.85 | 3.83 | 3.82 | 3.81 | 3.77 | 3.71 | 3.63 | 3.66 | 3.87 | 4.17 | 4.03 | 3.98 | 3.92 | 3.83 |
| 6 | 4.77 | 4.82 | 4.87 | 4.90 | 4.89 | 4.84 | 4.75 | 4.77 | 5.04 | 5.43 | 5.22 | 5.15 | 5.05 | 4.90 |
| 7 | 5.62 | 5.75 | 5.88 | 6.00 | 6.05 | 6.02 | 5.95 | 5.96 | 6.30 | 6.78 | 6.53 | 6.43 | 6.29 | 6.06 |
| 8 | 6.37 | 6.57 | 6.77 | 6.94 | 7.04 | 7.09 | 7.08 | 7.14 | 7.57 | 8.20 | 7.92 | 7.80 | 7.63 | 7.34 |
| 9 | 7.12 | 7.40 | 7.66 | 7.88 | 8.02 | 8.10 | 8.11 | 8.17 | 8.66 | 9.38 | 9.12 | 9.01 | 8.85 | 8.58 |
| 10 | 7.78 | 8.16 | 8.51 | 8.82 | 9.01 | 9.10 | 9.14 | 9.22 | 9.78 | 10.59 | 10.30 | 10.18 | 9.99 | 9.67 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.52 | 2.46 | 2.42 | 2.40 | 2.37 | 2.33 | 2.29 | 2.33 | 2.47 | 2.67 | 2.59 | 2.57 | 2.53 | 2.47 |
| 5 | 3.32 | 3.28 | 3.26 | 3.25 | 3.22 | 3.17 | 3.11 | 3.14 | 3.33 | 3.59 | 3.48 | 3.44 | 3.39 | 3.32 |
| 6 | 4.12 | 4.12 | 4.14 | 4.15 | 4.13 | 4.08 | 4.01 | 4.03 | 4.27 | 4.60 | 4.43 | 4.37 | 4.29 | 4.17 |
| 7 | 4.89 | 4.96 | 5.02 | 5.08 | 5.08 | 5.05 | 4.98 | 4.99 | 5.27 | 5.68 | 5.47 | 5.38 | 5.27 | 5.09 |
| 8 | 5.62 | 5.75 | 5.88 | 6.00 | 6.05 | 6.04 | 5.98 | 5.99 | 6.33 | 6.83 | 6.58 | 6.48 | 6.34 | 6.11 |
| 9 | 6.26 | 6.45 | 6.64 | 6.81 | 6.91 | 6.95 | 6.95 | 7.00 | 7.42 | 8.01 | 7.74 | 7.62 | 7.45 | 7.19 |
| 10 | 6.91 | 7.17 | 7.39 | 7.60 | 7.74 | 7.81 | 7.82 | 7.89 | 8.36 | 9.04 | 8.80 | 8.70 | 8.54 | 8.30 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 10.303 | 8.802 |
| SC2 | 0 | 8 | 7.138 | 5.991 |
| SC3 | -18 | 7 | 6.033 | 5.086 |
| SC4 | -25 | 6 | 4.866 | 4.137 |
| SC5 | -34 | 6 | 4.785 | 4.124 |
| A | 1017 mm |
|---|---|
| B | 560 mm |
| C | 617 mm |
| F | 445 mm |
| E | 685 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1017 mm |
|---|---|
| Width | 560 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.