EB-330BC6-B01 C
6.82 kW
Defrost: None
Product code: EB-330AC4-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,717 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 24.8 m² |
| Inner volume | 4.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 42 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 69.5 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EB-330AC4-B01 C | None |
|---|---|
| EB-330AC4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.86 | 2.91 | 2.96 | 3.00 | 3.01 | 3.00 | 2.97 | 3.02 | 3.22 | 3.48 | 3.40 | 3.37 | 3.34 | 3.29 |
| 5 | 3.60 | 3.72 | 3.83 | 3.93 | 3.98 | 3.99 | 3.97 | 4.02 | 4.27 | 4.63 | 4.50 | 4.45 | 4.38 | 4.29 |
| 6 | 4.22 | 4.41 | 4.59 | 4.74 | 4.84 | 4.90 | 4.92 | 4.99 | 5.31 | 5.76 | 5.63 | 5.58 | 5.51 | 5.39 |
| 7 | 4.85 | 5.11 | 5.35 | 5.56 | 5.69 | 5.78 | 5.82 | 5.90 | 6.27 | 6.81 | 6.65 | 6.59 | 6.49 | 6.33 |
| 8 | 5.39 | 5.74 | 6.07 | 6.35 | 6.55 | 6.67 | 6.73 | 6.82 | 7.24 | 7.87 | 7.68 | 7.60 | 7.49 | 7.29 |
| 9 | 5.88 | 6.34 | 6.75 | 7.12 | 7.38 | 7.51 | 7.61 | 7.73 | 8.21 | 8.92 | 8.73 | 8.64 | 8.51 | 8.27 |
| 10 | ≈ 6.33 | 6.89 | 7.41 | 7.80 | 8.14 | 8.36 | 8.50 | 8.65 | 9.20 | 10.00 | 9.79 | 9.70 | 9.54 | 9.27 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 9.794 |
| SC2 | 0 | 8 | 6.816 |
| SC3 | -18 | 7 | 5.625 |
| SC4 | -25 | 6 | 4.587 |
| SC5 | -34 | 6 | 4.268 |
| A | 1617 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1295 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1617 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.