EB-135AE4-B01 C
5.64 kW
Defrost: None
Product code: EB-330AC7-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,955 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 15.6 m² |
| Inner volume | 4.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 42 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.1 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EB-330AC7-B01 C | None |
|---|---|
| EB-330AC7-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.34 | 2.34 | 2.34 | 2.35 | 2.34 | 2.32 | 2.29 | 2.31 | 2.46 | 2.65 | 2.58 | 2.55 | 2.51 | 2.45 |
| 5 | 3.00 | 3.05 | 3.10 | 3.14 | 3.15 | 3.14 | 3.11 | 3.14 | 3.32 | 3.59 | 3.48 | 3.44 | 3.39 | 3.31 |
| 6 | 3.63 | 3.74 | 3.84 | 3.94 | 3.99 | 4.00 | 3.98 | 4.01 | 4.25 | 4.60 | 4.46 | 4.40 | 4.33 | 4.20 |
| 7 | 4.17 | 4.33 | 4.49 | 4.63 | 4.73 | 4.78 | 4.80 | 4.86 | 5.16 | 5.61 | 5.48 | 5.42 | 5.33 | 5.18 |
| 8 | 4.71 | 4.93 | 5.14 | 5.32 | 5.45 | 5.53 | 5.57 | 5.64 | 5.99 | 6.51 | 6.36 | 6.30 | 6.20 | 6.05 |
| 9 | 5.19 | 5.49 | 5.76 | 6.01 | 6.18 | 6.29 | 6.34 | 6.42 | 6.83 | 7.41 | 7.25 | 7.18 | 7.08 | 6.90 |
| 10 | 5.63 | 6.01 | 6.36 | 6.66 | 6.89 | 7.03 | 7.12 | 7.22 | 7.65 | 8.31 | 8.15 | 8.07 | 7.95 | 7.75 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.147 |
| SC2 | 0 | 8 | 5.639 |
| SC3 | -18 | 7 | 4.674 |
| SC4 | -25 | 6 | 3.841 |
| SC5 | -34 | 6 | 3.657 |
| A | 1617 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1295 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1617 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.